Permit Information
Permit NumberMEC16-05454
StatusFinaled
Name ADVANCED HEATING & COOLING
Site Address 505 W BROAD ST
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Supply and install all HVAC systems, labor, materials, and equipment. HVAC equipment, accessories, and components. ERU MAU, heat pumps, fans, heaters, louvers, ductwork, registers, grilles, dampers, drain pans, and condensing units.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/7/20183/7/20183/7/2018PPASS
DetailsChad Schwendiman
Final3/7/20183/7/20183/7/2018ACANC
DetailsChad Schwendiman
Final inspections for 710 610 510 410 310. Please contact Rob with any questions or concerns ###-#### Inspection requested via web by Heather Gransbery
Final3/6/20183/6/20183/6/2018PCANC
DetailsChad Schwendiman
Final inspections for 710 610 510 410 310. Please contact Rob with any questions or concerns. Inspection requested via web by Heather Gransbery
Final3/5/20183/5/20183/5/2018PFAIL
DetailsChad Schwendiman
Final inspections for 710 610 510 410 310. Please contact Rob with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Anderson construction need to submit final LEED's commisioning report to boise city before we can final permit out.
Final3/2/20183/2/20183/2/2018PFAIL
DetailsChad Schwendiman
Final inspection for 710,610,510,410,310. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - air balancing not complete
Final3/1/20183/2/20183/2/2018AFAIL
DetailsChad Schwendiman
Final inspection requested for 710 610 510 410 310 Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Jess Wigley - air balance needs to be completed.
Final2/28/20183/1/20183/1/2018ACANC
DetailsChad Schwendiman
Final inspection for 710 610 510 410 310. Previously request for 02/08 AM. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
Final2/28/20182/28/20182/28/2018PCANC
DetailsChad Schwendiman
Request for final inspection Live Works. Please contact Rob ###-#### with any question or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - This is the wrong permit number. comments entered under correct permit number
Final2/15/20182/16/20182/16/2018APART
DetailsChad Schwendiman
Request for inspector to sign off on card for occupancy for levels 3;4. Had final and passed, but need inspector signature.
Phone #: ###-#### Inspection requested via web by Heather Gransbery - Signed the card
Final2/9/20182/9/20182/9/2018PPART
DetailsChad Schwendiman
3rd & 4th floors - Temporary occupancy okay for 3rd, and 4th floors
Final2/9/20182/12/20182/9/2018ACANC
DetailsChad Schwendiman
Request for 3rd floor final inspection. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
Final2/8/20182/8/20182/8/2018APEND
DetailsChad Schwendiman
Final inspection request for 710,610,510,410,310. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Need a updated air balance report
Final2/2/20182/2/20182/2/2018PPART
DetailsChad Schwendiman
Request for final Floors 5,6,7. Please contact Rob with any questions or concerns ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - temporary occupancy okay for 5th, 6th, and 7th floors.
Final1/25/20181/26/20181/26/2018AFAIL
DetailsChad Schwendiman
Request for Final/TCO on Fl 1, 2, 5, 6, 7. Please contact Rob with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Need a copy of the air balance report for all area's being occupied. Need approved TCO plan from building official. Need to extend fresh air opening on roof.
Final1/16/20181/17/20181/17/2018APART
DetailsChad Schwendiman
Request for Final inspection on 3rd floor. No inspection on RM 310 and 321. Please contact Rob with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - 3rd floor units okay except for 310, 321, unjt 401, 501, 520, 534, (This activity was added in error so we have changed the case status back to Issued.)
CHANGE STATUS TO (ISS)  1/17/2018 DONE
per Chad S. finaled by mistake. Final insp was a PART
Final1/15/20181/16/20181/16/2018ACANC
DetailsChad Schwendiman
Request for Final inspection on 3rd Floor. No inspection on Rm 310 and 321. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
Final1/12/20181/12/20181/12/2018APART
DetailsChad Schwendiman
Request for final inspection on 4th floor. Please contact Rob with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - Still need air balance report to final out units, 4th foor units okay except for 410, 401. 705 okay as well
Final1/4/20181/5/20181/5/2018APEND
DetailsChad Schwendiman
Request for final inspection on 6th and 7th floors, except 610 and 710. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Still need air balance reports to be able to final rooms out. 7th floor east rooms okay except for 705, 710, 734. 6th floor east rooms okay except 610, 634. 5th floor rooms okay except for 501, 510, 514, 520, 534. corridoor
Rough-in12/29/201712/29/201712/29/2017PPASS
DetailsChad Schwendiman
request for R/I inspection on live works. Please contact Rob with any questions or concerns ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
Rough-in12/12/201712/12/201712/12/2017PPASS
DetailsTroy James
Request for R/I inspection 3rd floor Community Room 321. Please contact Rob with any questions or concerns. ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery
Final12/12/201712/12/201712/12/2017PPART
DetailsTroy James
Request for final 7th floor utility room. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
Rough-in12/8/201712/8/201712/8/2017PFAIL
DetailsChad Schwendiman
Request for inspection Community Room RM 321. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Need to complete sealing duct work. need supports on duct work need angle on fire damper
Rough-in11/20/201711/20/201711/20/2017PPASS
DetailsChad Schwendiman
request for ceiling inspection. Please contact Rob, ###-####, with any questions or concerns. If possible, AM inspection, missed deadline by 5 minutes. Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover ceilings in the live work units on 5th street side
Conference11/6/201711/6/201711/6/2017ACANC
DetailsChad Schwendiman
Rob ###-####
Rough-in10/10/201710/11/201710/11/2017APASS
DetailsChad Schwendiman
Request for inspection 3rd floor R/I. Please contact Juan, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 3rd floor apartments okay
Rough-in10/4/201710/5/201710/5/2017APART
DetailsBen Livingston
Request for inspection 3rd floor. Please contact job lead, Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
All rooms on 3rd floor accept 306
Rough-in9/25/20179/26/20179/26/2017ACANC
DetailsChad Schwendiman
request for inspection on MA shaft. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
Rough-in9/25/20179/25/20179/25/2017APART
DetailsChad Schwendiman
Request for MA shaft inspection and inspection on 4th Floor apts. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 4th floor apartments okay. Need to install fire/smoke dampers prior to rough in
Rough-in9/25/20179/25/20179/25/2017ACANC
DetailsChad Schwendiman
Request for inspection 4th floor apts. Please contact Rob, ###-#### with any questions or concerns. Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
Rough-in9/21/20179/21/20179/21/2017ACANC
DetailsChad Schwendiman
Rob ###-####
Rough-in9/19/20179/19/20179/19/2017PPASS
DetailsChad Schwendiman
Request for R/I inspection 4th floor. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 4th floor units 02, 04, 06, 07, 09, 10, 11, 12, 14, 16, 18, 21, 22
Rough-in9/18/20179/18/20179/18/2017APASS
DetailsChad Schwendiman
request for r/I inspection 4th and 5th floors. Please contact Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 5th floor Units 07, 01, 21, 22 4th floor units 01, 05, 08 13, 15 17, 19, 20
Rough-in9/14/20179/14/20179/14/2017ACANC
DetailsBen Livingston
Request for R/I 5th floor. Contact job lead, Rob, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
Rough-in9/12/20179/13/20179/13/2017APART
DetailsBen Livingston
R/I inspection 5th floor. Please contact job lead, Rob, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
rooms 502,504,506 okay
Rough-in9/7/20179/7/20179/7/2017PPART
DetailsBen Livingston
request for inspection, 5th Floor. Please contact Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
505,506,519 okay
Rough-in9/5/20179/6/20179/6/2017APASS
DetailsChad Schwendiman
Request for r/I above ceiling inspection on 2nd floor and 5th floor. Please contact Rob, ###-####, with questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 5th floor units 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 20
Rough-in8/31/20179/1/20179/1/2017APASS
DetailsChad Schwendiman
request for 7th floor inspection. Please contact Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 722, 721
Rough-in8/30/20178/31/20178/31/2017PPASS
DetailsChad Schwendiman
Request for R/I 7th floor inspection. Please contact Rob, ###-####. with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery sub duct shaft 32 seal and caulk
Rough-in8/28/20178/29/20178/29/2017APASS
DetailsChad Schwendiman
Request for R/I 7th Floor apts. Contact Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 7th floor units 10, 12, 14, 16, 17, 18, 19, 20 okay to cover
Rough-in8/24/20178/25/20178/25/2017APASS
DetailsChad Schwendiman
Request for R/I inspections 7th floor apartments. Please call Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 7th floor units 9, 11, 13, 15 okay to cover
Rough-in8/22/20178/23/20178/23/2017APASS
DetailsChad Schwendiman
Request for east side of building 4-7th inspection on shafts. Please contact Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - subduct shaft 21 complete
Rough-in8/22/20178/22/20178/22/2017APASS
DetailsChad Schwendiman
Request for inspection on 4-7th shafts, east side of building. Please contact Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Sub duct shaft 21 seal & caulk okay
Rough-in8/15/20178/15/20178/15/2017APART
DetailsTroy James
Request for inspection on 2nd Floor shaft. Please call Juan ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
Ok access doors to shaft 5th and broad corner. Framing is required to be done per manufacturer instructions for the second level shaft. supply and exhaust duct.
Rough-in8/4/20178/7/20178/7/2017PCANC
DetailsChad Schwendiman
Request for shaft inspection 3rd through 7th floors. Please contact job lead Rob, ###-####, with any questions or concerns. Inspection requested via web by Heather Gransbery
Rough-in8/4/20178/7/20178/7/2017APASS
DetailsChad Schwendiman
Request for shaft inspection 3rd through 7th floor. Please contact job lead Rob, ###-####, with any questions or concerns. Inspection requested via web by Heather Gransbery - sub duct sahft 5 complete
Rough-in8/4/20178/4/20178/4/2017PPASS
DetailsChad Schwendiman
Request for inspection floors 3 through 7 shaft. Please contact job lead, Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - sub duct shaft 5 seal and caulk okay
Rough-in8/3/20178/4/20178/4/2017APASS
DetailsChad Schwendiman
Request for inspection on 6th Floor Apts. Please contact job lead, Rob, with any questions or concerns###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover units 602, and 606
Rough-in8/3/20178/3/20178/3/2017PCANC
DetailsChad Schwendiman
Request for inspection on 6th Floor Apts. Please contact job lead, Rob, with any questions or concerns. ###-#### Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
Rough-in8/3/20178/3/20178/3/2017APASS
DetailsChad Schwendiman
R/I AM inspection request for 6th floor.
Job lead contact is Rob Campbell ###-#### Phone #: ###-#### Inspection requested via web by Jess Wigley - ceiling okay to cover in unit 615
Rough-in8/1/20178/2/20178/3/2017PPASS
DetailsChad Schwendiman
Request for cover inspection on 6th floor rooms. Please contact job lead, Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover ceilings in units 604, 607, 608, 611, 613
Rough-in7/27/20177/27/20177/27/2017PPASS
DetailsChad Schwendiman
Request for inspection on 3rd -7th Floor shafts. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - sub duct shafts complete 1,4,6,25 3rd through 7th floors. ceilings okay to cover in 609, 612, 614
Rough-in7/26/20177/27/20177/27/2017ACANC
DetailsChad Schwendiman
Request for shaft inspection 3rd Floor through 7th Floor. Please contact Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
Rough-in7/25/20177/26/20177/26/2017APASS
DetailsChad Schwendiman
Request for inspection on 3rd -7th Floor shafts. Please contact Rob ###-#### with any questions or concerns.
Phone #: ###-#### Inspection requested via web by Heather Gransbery - Sub duct shafts seal and caulk oaky on 4,6,1,25 3rd floor though 7th. sub duct shafts complete on 7,9,24,23 3rd floor through 7th.
Rough-in7/24/20177/25/20177/25/2017ACANC
DetailsChad Schwendiman
Request for inspection on 3rd -7th Floor shafts. Request for above ceiling inspection on 6th Floor apartment. Please contact job lead, Rob, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
Rough-in7/24/20177/24/20177/24/2017APASS
DetailsChad Schwendiman
Sub duct shafts from 3rd floor to 7th floor seal and fire caulk okay units 9,7,6,4,3,2,1,22,23,24. Mian shaft okay to cover o 3rd, 4th, 5th, and 6th floor.
Rough-in7/14/20177/14/20177/14/2017APASS
DetailsBen Livingston
R/I inspection on shaft 3 through 7th floors. Please contact job lead, Rob, with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
subduct liner 11 complete 3rd to 7thfloor
Inspection copied from MEC16-05130
Rough-in7/13/20177/14/20177/14/2017APART
DetailsBen Livingston
R/I inspection on shaft 3 through 7th floors. Please contact job lead, Rob, with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather
Gransbery
subduct liner 8,10 complete
subduct 11 seal and caulk 3rd to 7th floor
Inspection copied from MEC16-05130
Rough-in7/13/20177/13/20177/14/2017APART
DetailsBen Livingston
R/I inspection on shaft 3 through 7th floors. Please contact job lead, Rob, with any questions or concerns Phone #: ###-#### Inspection requested via web by Heather Gransbery
subduct liner 8,10 seal and caulk okay
subduct liner 12,14, 13,15 17 19 complete 3rd floor to 7th
Inspection copied from MEC16-05130
Rough-in7/12/20177/12/20177/12/2017APART
DetailsBen Livingston
R/I inspection on shaft 3 through 7th floors. Please contact job lead, Rob, with any questions or concerns Phone #: ###-#### Inspection requested via web by Heather Gransbery
shaft liner 20,18,16 complete
shaft liner 12,14,19 seal and caulk
Inspection copied from MEC16-05130
Rough-in7/10/20177/11/20177/11/2017ANR
DetailsBen Livingston
R/I inspection on shaft 3 through 7th floors. Please contact job lead, Rob, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery

Inspection copied from MEC16-05130
Rough-in7/10/20177/10/20177/10/2017APART
DetailsBen Livingston
R/I inspection on shaft 3 through 7th floors. Please contact job lead, Rob, with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
subduct rooms 20,18,16,15 3rd floor to 7th seal and firecaulk inside okay
rooms 17,19 exhaust duct 3rd floor to 7th ok to start subduct ** Inspection copied from MEC16-05130
Mec-Aging Inspection7/6/20177/6/20177/6/2017 CANC
DetailsChad Schwendiman
Issue PAID IN FULL permit  12/7/2016 DONE
Payment received via Govolutions
Application received  12/7/2016 DONE
This permit was created on the web by Heather Gransbery
First Notice3/7/20183/7/2018   
DetailsChad Schwendiman
First Notice1/17/20181/17/2018   
DetailsChad Schwendiman