First Notice | 6/30/2017 | 6/30/2017 | 12/12/2017 | | DONE |
Chad Schwendiman
|
|
|
|
Print Statement | | | 12/12/2017 | | DONE |
|
|
|
|
Final | 6/29/2017 | 6/30/2017 | 6/30/2017 | A | PASS |
Chad Schwendiman
|
|
|
Final inspection needed for Boise Centre Ph 3 if you need to contact someone please call Karl at ###-#### thank you Phone #: ###-#### Inspection requested via web by Karl Hestekin
|
Rough-in | 6/23/2017 | 6/26/2017 | 6/26/2017 | A | PASS |
Ben Livingston
|
|
|
Cover inspection needed Monday A.M.At Boise Centre Brad is available to contact at ###-#### if unable to reach Brad you may contact Karl at ###-#### thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin missing grilles okay
|
Final | 6/21/2017 | 6/22/2017 | 6/22/2017 | P | FAIL |
Chad Schwendiman
|
|
|
Partial above Grid inspection Phone #: ###-#### Inspection requested via web by Karl Hestekin - random grills not connected
|
Rough-in | 6/22/2017 | 6/22/2017 | 6/22/2017 | P | CANC |
Chad Schwendiman
|
|
|
Good morning can I get a partial grid inspection for Boise Centre Thank you P.M. if possible Phone #: ###-#### >> Inspection requested via web by Karl Hestekin Inspection cancelled from web by: Karl Hestekin
|
Rough-in | 6/13/2017 | 6/14/2017 | 6/14/2017 | A | PASS |
Chad Schwendiman
|
|
|
Need a rough-in inspection for Boise Centre Ph 3 06/14/2017 A.M. preferred if possible.Please contact Rob ###-#### or Karl at ###-#### if there are any questions or concerns thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin - mechanical room duct work okay
|
Rough-in | 6/9/2017 | 6/9/2017 | 6/9/2017 | P | PASS |
Chad Schwendiman
|
|
|
Need a partial fire inspection as soon as you can. questions call Rob at ###-#### or Karl at ###-#### Phone #: ###-#### Inspection requested via web by Karl Hestekin - Framing around fire dampers okay
|
Rough-in | 6/2/2017 | 6/5/2017 | 6/5/2017 | A | FAIL |
Chad Schwendiman
|
|
|
Need a partial fire damper inspection for A.M. if there are any questions contact Karl at ###-#### Phone #: ###-#### Inspection requested via web by Karl Hestekin - Need framing on all 4 sides of dampers per manufactures instructions
|
Rough-in | 5/31/2017 | 5/31/2017 | 5/31/2017 | P | PART |
Chad Schwendiman
|
|
|
We will need a fire damper inspection for Boise Center on the Grove if you have any questions please call Karl at ###-#### thank you Phone #: ###-#### Inspection requested via web by Karl Hestekin - fire dampers for exhaust okay
|
Rough-in | 5/25/2017 | 5/26/2017 | 5/26/2017 | A | FAIL |
Chad Schwendiman
|
|
|
Fire damper inspection needed for Boise Centre Ph 3 please contact Karl Hestekin with any questions at ###-#### or Rob at ###-#### A.M.preferred thank you:) Phone #: ###-#### Inspection requested via web by Karl Hestekin - Fire dampers still not installed per instructions
|
Rough-in | 5/15/2017 | 5/15/2017 | 5/15/2017 | P | PART |
Chad Schwendiman
|
|
|
Can I please get a rough in inspection for Boise Centre on the Grove for 12:30 pm if possible thank you:) If you have questions please call Karl at ###-#### Phone #: ###-#### Inspection requested via web by Karl Hestekin - okay to cover hard lids on 1st floor. Need to install fire/smoke dampers per manufactures instructions
|
Telephone call | | | 5/12/2017 | | DONE |
|
|
|
called Karl to see of they finished the job of if American Chiller did. I told Cathy that if they finished the job for KMD Mech they needed to pull there own permit
|
Final | 3/30/2017 | 3/30/2017 | 3/30/2017 | P | CANC |
Chad Schwendiman
|
|
|
Need a final inspection for Kendall Ph 3 P.m 29th thank you Contact Karl Hestekin ###-#### Phone #: ###-#### Inspection requested via web by Karl Hestekin
|
CHANGE STATUS TO (ISS) | | | 3/7/2017 | | DONE |
|
|
|
|
Hold | | | 2/7/2017 | | DONE |
|
|
|
Building permit needs issued
|
Issue PAID IN FULL permit | | | 2/2/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/2/2017 | | DONE |
|
|
|
This permit was created on the web by Karl Hestekin
|