Final | 6/6/2017 | 6/7/2017 | 6/7/2017 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka
|
Final | 6/5/2017 | 6/6/2017 | 6/6/2017 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- fresh air needs insulated in garage to R/A plenum- need fire caulk on pvc flue in garage at ceiling- need to seal lineset penetration thru foundation- need uv protection on line set at A/C- need 3 screws on water heater vent at china cap- left correction notice on front of furnace
|
Final | 6/1/2017 | 6/1/2017 | 6/1/2017 | P | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by dannyel chaloupka Inspection cancelled from web by: dannyel chaloupka
|
Final | 5/31/2017 | 6/1/2017 | 6/1/2017 | A | CANC |
Brian Scoles
|
|
|
>> Inspection requested via web by dannyel chaloupka Inspection cancelled from web by: dannyel chaloupka
|
Rough-in | 3/8/2017 | 3/9/2017 | 3/9/2017 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- 5lb flue pass
|
Rough-in | 3/7/2017 | 3/8/2017 | 3/8/2017 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- need insulation shield above sheetrock in garage around b vent- flue test fail- stuck on 6.5 psi
|
Pressure Test | 3/7/2017 | 3/8/2017 | 3/8/2017 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- 20lb gas pass
|
Issue PAID IN FULL permit | | | 2/21/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/20/2017 | | DONE |
|
|
|
This permit was created on the web by Debbie Marino
|