Final | 10/12/2017 | 10/13/2017 | 10/13/2017 | A | PASS |
Brian Scoles
|
|
|
thank you Phone #: ###-#### Inspection requested via web by Aaron Alandt
|
Final | 10/11/2017 | 10/12/2017 | 10/12/2017 | A | FAIL |
Brian Scoles
|
|
|
Inspection requested via web by Aaron Alandt- need to seal and insulater outside air in furnace closet- need gas line hooked up to water heater- water heater flue needs 6" clearance to sheetrock for single wall pipe- left correction notice front of furnace-
|
Rough-in | 6/26/2017 | 6/27/2017 | 6/27/2017 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Ben Welgan- 20lb gas pass- 5lb flue pass- R/I ok
|
Rough-in | 6/26/2017 | 6/26/2017 | 6/26/2017 | P | FAIL |
Brian Scoles
|
|
|
LATE PM IF POSSIBLE PLEASE THANK YOU Phone #: ###-#### Inspection requested via web by Ben Welgan- need to test pvc flue runs in conditioned space
|
Pressure Test | 6/23/2017 | 6/23/2017 | 6/23/2017 | P | PASS |
Troy James
|
|
|
Phone #: ###-#### Inspection requested via web by Ben Welgan 20# test
|
Rough-in | 6/23/2017 | 6/23/2017 | 6/23/2017 | P | FAIL |
Troy James
|
|
|
Phone #: ###-#### Inspection requested via web by Ben Welgan
Need to connect exhaust fans. Ducts in crawl are to be installed with no dips/sagging.
|
Issue PAID IN FULL permit | | | 5/26/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/26/2017 | | DONE |
|
|
|
This permit was created on the web by Ben Welgan
|