Final | 10/2/2017 | 10/3/2017 | 10/3/2017 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka
|
Conference | 7/27/2017 | 7/27/2017 | 7/27/2017 | A | PASS |
Brian Scoles
|
|
|
w duct blast 930 am Phone #: ###-#### Inspection requested via web by dannyel chaloupka- 61cfm loss
|
Conference | 7/25/2017 | 7/26/2017 | 7/26/2017 | A | FAIL |
Brian Scoles
|
|
|
witness duct blast 930 am Phone #: ###-#### Inspection requested via web by dannyel chaloupka- duct blast failed- 118 cfm loss needs to be no more than 103 cfm
|
Rough-in | 7/20/2017 | 7/20/2017 | 7/20/2017 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- need to strap up lineset in crawl before final- no framing around b vent to water heater in garage per builder
|
Rough-in | 7/19/2017 | 7/19/2017 | 7/19/2017 | P | NR |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- framimg removed from b vent for water- need to install??
|
Rough-in | 7/17/2017 | 7/18/2017 | 7/18/2017 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- framing around b vent for water heater does not meet clearances- duct work ran back in same location on TGIs that was pulled down- talked with Zac about this and texted him pics
|
Pressure Test | 7/17/2017 | 7/18/2017 | 7/18/2017 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- 20lb gas pass whole system retested to fireplace
|
Conference | 7/14/2017 | 7/14/2017 | 7/14/2017 | A | PASS |
Brian Scoles
|
|
|
Called Dannyel at TML to talk about ducting that was pulled down and gas line to fireplace needs finished- she will reschedule R/I inspection
|
Rough-in | 7/11/2017 | 7/12/2017 | 7/12/2017 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka
|
Rough-in | 7/11/2017 | 7/11/2017 | 7/11/2017 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- Fresh air to return air plenum needs to be ran in insulated flex in garage, unconditioned space-
|
Pressure Test | 7/11/2017 | 7/11/2017 | 7/11/2017 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- 20lb gas pass
|
Pressure Test | 7/10/2017 | 7/11/2017 | 7/11/2017 | A | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by dannyel chaloupka Inspection cancelled from web by: dannyel chaloupka
|
Rough-in | 7/10/2017 | 7/11/2017 | 7/11/2017 | A | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by dannyel chaloupka Inspection cancelled from web by: dannyel chaloupka
|
Rough-in | 7/10/2017 | 7/10/2017 | 7/10/2017 | P | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by dannyel chaloupka Inspection cancelled from web by: dannyel chaloupka
|
Pressure Test | 7/10/2017 | 7/10/2017 | 7/10/2017 | P | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by dannyel chaloupka Inspection cancelled from web by: dannyel chaloupka
|
Issue PAID IN FULL permit | | | 6/26/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/26/2017 | | DONE |
|
|
|
This permit was created on the web by Debbie Marino
|