Final | 10/5/2017 | 10/5/2017 | 10/5/2017 | A | PASS |
Ben Livingston
|
|
|
Please text me 1hr. before the estimated inspection time. 208.412.6713 Thank you!! Phone #: ###-#### Inspection requested via web by Richard Cusimano
|
Final | 9/25/2017 | 9/25/2017 | 9/25/2017 | A | FAIL |
Ben Livingston
|
|
|
Garage code 2770. Phone #: ###-#### Inspection requested via web by Richard Cusimano fresh air needs to be ins. in mechanical closet, couldnt find blast test or balance report
|
(F) Reprint permit | | | 7/25/2017 | | DONE |
|
|
|
|
Rough-in | 7/24/2017 | 7/24/2017 | 7/24/2017 | P | PASS |
Brian Scoles
|
|
|
robert 208 412 6713- furnace and ac not set yet- contractor working with builder in furnace/linen closet upstairs will be complete by final-
|
Pressure Test | 7/24/2017 | 7/24/2017 | 7/24/2017 | P | PASS |
Brian Scoles
|
|
|
2olb gas pass- 5lb flue pass
|
Rough-in | 7/21/2017 | 7/24/2017 | 7/24/2017 | A | FAIL |
Brian Scoles
|
|
|
Richard Phone #: ###-####- gas at zero needs 30lb guage not 15lb- csst cant penetrate appiance fireplace with protective sleeve- need to pressure test flue 2nd floor- need approved nail plate in laundry room for csst gas piping- dryer vent is oval at top plate need to maintain 4" round- exhaust duct in laundry room needs supported- master bedroom need RA or transfer grill installed not shown on manual J- supply main 2nd floor needs finished to furnace room-lineset needs strapped up in attic- bedroom 2nd floor west side needs supply register leveled and supported better at ceiling- supply joints needs sealed 2nd floor on elbows- left correction notice in garage on supply line
|
Pressure Test | 7/21/2017 | 7/24/2017 | 7/24/2017 | A | FAIL |
Brian Scoles
|
|
|
Richard Phone #: ###-####- gas guage a 0 and needs to be 30lb guage not 15 lb- flue needs tested 2nd floor
|
Issue PAID IN FULL permit | | | 7/21/2017 | | DONE |
|
|
|
|
Application received | | | 7/20/2017 | | DONE |
|
|
|
This permit was created on the web by Richard Cusimano
|