Final | 8/28/2017 | 8/29/2017 | 8/29/2017 | P | PASS |
Brian Scoles
|
|
|
mechanical fireplace final inspection Phone #: ###-#### Inspection requested via web by Dan Otero
|
Rough-in | 8/11/2017 | 8/11/2017 | 8/11/2017 | P | PASS |
Brian Scoles
|
|
|
fireplace R/I ok
|
Rough-in | 8/7/2017 | 8/8/2017 | 8/8/2017 | A | FAIL |
Brian Scoles
|
|
|
Late AM inspection if possible Phone #: ###-#### Inspection requested via web by Dan Otero- need to add pressure test to permit- guage doesnt zero out- need sleeve on csst piping where pentrates appliance- needs dante valve installed in floor- retest system when completed with work and call in inspection- R/I on fireplace ok
|
Issue PAID IN FULL permit | | | 7/24/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/24/2017 | | DONE |
|
|
|
This permit was created on the web by Dan Otero
|