Final | 11/22/2017 | 11/22/2017 | 11/22/2017 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka
|
Final | 11/21/2017 | 11/21/2017 | 11/21/2017 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- need duct blast completed and signed off to final out
|
Rough-in | 9/6/2017 | 9/7/2017 | 9/7/2017 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka
|
Rough-in | 9/6/2017 | 9/6/2017 | 9/6/2017 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- duct in crawl needs supported per manufactures install and off ground middle to south end of house- reinspection fee added
|
Pressure Test | 9/6/2017 | 9/6/2017 | 9/6/2017 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- 20lb gas pass
|
Rough-in | 9/5/2017 | 9/6/2017 | 9/6/2017 | A | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by dannyel chaloupka Inspection cancelled from web by: dannyel chaloupka
|
Rough-in | 9/5/2017 | 9/5/2017 | 9/5/2017 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- need approved manual J onsite for inspection
|
Pressure Test | 9/5/2017 | 9/5/2017 | 9/5/2017 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- gauge at 6psi
|
Rough-in | 8/31/2017 | 9/1/2017 | 9/1/2017 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- need approved manual J onsite- need to hook up exhaust fan- need 1" clearance on b vent at roof, to sheetrock and from armor flex and support b vent better- insulation shield cant be out of adjustable 90 degree
|
Pressure Test | 8/31/2017 | 9/1/2017 | 9/1/2017 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- gas pressure below 20lb
|
Issue PAID IN FULL permit | | | 8/21/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/18/2017 | | DONE |
|
|
|
This permit was created on the web by Debbie Marino
|