Permit Information
Permit NumberMEC17-03733
StatusFinaled
Name TML LLC
Site Address 4724 S SPOTTED HORSE AVE
Project Name 
Customer Number22093-23
ePlanReviewNo
Description
Complete HVAC Installation: New HVAC system
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/22/201711/22/201711/22/2017PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by dannyel chaloupka
Final11/21/201711/21/201711/21/2017AFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- need duct blast completed and signed off to final out
Rough-in9/6/20179/7/20179/7/2017APASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by dannyel chaloupka
Rough-in9/6/20179/6/20179/6/2017PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- duct in crawl needs supported per manufactures install and off ground middle to south end of house- reinspection fee added
Pressure Test9/6/20179/6/20179/6/2017PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- 20lb gas pass
Rough-in9/5/20179/6/20179/6/2017ACANC
DetailsBrian Scoles
Phone #: ###-#### >> Inspection requested via web by dannyel chaloupka Inspection cancelled from web by: dannyel chaloupka
Rough-in9/5/20179/5/20179/5/2017PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- need approved manual J onsite for inspection
Pressure Test9/5/20179/5/20179/5/2017PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- gauge at 6psi
Rough-in8/31/20179/1/20179/1/2017AFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- need approved manual J onsite- need to hook up exhaust fan- need 1" clearance on b vent at roof, to sheetrock and from armor flex and support b vent better- insulation shield cant be out of adjustable 90 degree
Pressure Test8/31/20179/1/20179/1/2017AFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- gas pressure below 20lb
Issue PAID IN FULL permit  8/21/2017 DONE
Payment received via Govolutions
Application received  8/18/2017 DONE
This permit was created on the web by Debbie Marino