Final | 11/14/2017 | 11/16/2017 | 11/16/2017 | A | PASS |
Brian Scoles
|
|
|
Call jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek
|
Rough-in | 9/19/2017 | 9/20/2017 | 9/20/2017 | A | PASS |
Chad Schwendiman
|
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek
|
Rough-in | 9/12/2017 | 9/13/2017 | 9/13/2017 | A | FAIL |
Eric Strole
|
|
|
Call jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek-Need to complete rough-in. (crawl space) Missing nailplates on gas-tite. Furnace closet needs furred out for clearances to front of furnace.
|
Pressure Test | 9/12/2017 | 9/13/2017 | 9/13/2017 | A | PASS |
Eric Strole
|
|
|
Call jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek-20 lb gas test pass
|
Rough-in | 9/7/2017 | 9/8/2017 | 9/8/2017 | A | FAIL |
Brian Scoles
|
|
|
Call jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- need combustion air in furnace closet- need ex fans installed and hooked up- furnace closet needs furred out for clearances to front of furnace- need transfer grill installed in laundry closet- gas line reroute- left correction notice front window and taslked with installer onsite
|
Pressure Test | 9/7/2017 | 9/8/2017 | 9/8/2017 | A | CANC |
Brian Scoles
|
|
|
Call jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- per builder need to reroute gas line and omit gas to water heater going with electric
|
Issue PAID IN FULL permit | | | 9/7/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/7/2017 | | DONE |
|
|
|
This permit was created on the web by Dawn Kalsbeek
|