Card not on site to sign | 1/11/2018 | 1/11/2018 | 1/11/2018 | P | PASS |
Brian Scoles
|
|
|
no card to sign
|
Final | 1/10/2018 | 1/11/2018 | 1/11/2018 | A | PASS |
Brian Scoles
|
|
|
PLEASE CALL MIKE 1/2 HR BEFORE INSPECTION - ###-#### Phone #: ###-#### Inspection requested via web by Bryan Palmer- air balance ok- radiant dampers ok- no card to sign on site
|
Final | 1/8/2018 | 1/9/2018 | 1/9/2018 | A | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Bryan Palmer- need combustion air in furnace closet- single wall flue pipe needs 6" clearance to combustibles- need air balance report- need installation instruction on Radiant dampers- talked with Mike and installers about issues-
|
Pressure Test | 10/12/2017 | 10/13/2017 | 10/13/2017 | A | PASS |
Alan Hauser
|
|
|
20#
|
Rough-in | 10/2/2017 | 10/2/2017 | 10/2/2017 | A | PASS |
Alan Hauser
|
|
|
radiant fire dampers not to be here for 4 weeks. all else ok, will look at dampers on final
|
Conference | 9/29/2017 | 10/2/2017 | 10/2/2017 | A | PASS |
Alan Hauser
|
|
|
talked to hvac person about radiand fire dampers
|
Issue PAID IN FULL permit | | | 9/12/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/12/2017 | | DONE |
|
|
|
This permit was created on the web by Bryan Palmer
|
First Notice | 1/11/2018 | 1/11/2018 | | | |
Brian Scoles
|
|
|
|