Final | 11/15/2017 | 11/15/2017 | 11/15/2017 | P | PASS |
Alan Hauser
|
|
|
|
Rough-in | 11/14/2017 | 11/15/2017 | 11/15/2017 | A | PASS |
Alan Hauser
|
|
|
|
Issue PAID IN FULL permit | | | 10/30/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/30/2017 | | DONE |
|
|
|
This permit was created on the web by Jason Robinson
|