Final | 12/29/2017 | 1/2/2018 | 1/2/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart
|
Rough-in | 11/8/2017 | 11/9/2017 | 11/9/2017 | A | PASS |
Alan Hauser
|
|
|
|
Issue PAID IN FULL permit | | | 11/8/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/8/2017 | | DONE |
|
|
|
This permit was created on the web by Randy Hart
|