Final | 4/18/2018 | 4/18/2018 | 4/18/2018 | A | PASS |
Eric Strole
|
|
|
|
Rough-in | 4/17/2018 | 4/18/2018 | 4/18/2018 | A | CANC |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Dan Otero
|
Rough-in | 11/28/2017 | 11/29/2017 | 11/29/2017 | A | PASS |
Eric Strole
|
|
|
mechanical fireplace rough in inspection Phone #: ###-#### Inspection requested via web by Dan Otero
|
Issue PAID IN FULL permit | | | 11/22/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/22/2017 | | DONE |
|
|
|
This permit was created on the web by Dan Otero
|