Final | 3/27/2018 | 3/27/2018 | 3/27/2018 | P | PASS |
Ben Livingston
|
|
|
LATE PM. MAY CALL DANIEL WHEN ON WAY ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss
|
Final | 3/26/2018 | 3/27/2018 | 3/27/2018 | A | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss armaflex needs uv protection
|
Rough-in | 12/18/2017 | 12/18/2017 | 12/18/2017 | A | PASS |
Eric Strole
|
|
|
|
Final | 12/15/2017 | 12/18/2017 | 12/18/2017 | A | CANC |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss
|
Pressure Test | 12/15/2017 | 12/15/2017 | 12/15/2017 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss - 20lb gas, 5lb flue x2 pass
|
Rough-in | 12/15/2017 | 12/15/2017 | 12/15/2017 | P | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss - Missing transfer grill in guest bedroom, Ductwork not routed per approved manual J. Need to revise manual J and resubmit for approval
|
Issue PAID IN FULL permit | | | 12/5/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/5/2017 | | DONE |
|
|
|
This permit was created on the web by Krista Boss
|