Final | 4/10/2018 | 4/10/2018 | 4/10/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- final ok
|
Final | 4/6/2018 | 4/9/2018 | 4/9/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino- need uv protection on line set at AC-
|
Conference | 4/6/2018 | 4/9/2018 | 4/9/2018 | A | PASS |
Brian Scoles
|
|
|
Duct Blast at 10am. Gerry ###-#### Phone #: ###-#### Inspection requested via web by Debbie Marino- duct blast test pass
|
Final | 4/6/2018 | 4/9/2018 | 4/6/2018 | A | CANC |
Brian Scoles
|
|
|
Garage code #1234 Phone #: ###-#### >> Inspection requested via web by Debbie Marino Inspection cancelled from web by: Debbie Marino
|
Conference | 4/4/2018 | 4/5/2018 | 4/5/2018 | A | FAIL |
Brian Scoles
|
|
|
w duct blast 10 am Phone #: ###-#### Inspection requested via web by dannyel chaloupka- to much loss need to fix leaks
|
Conference | 3/20/2018 | 3/22/2018 | 3/22/2018 | P | CANC |
Brian Scoles
|
|
|
W Duct Blast 230 pm Phone #: ###-#### Inspection requested via web by dannyel chaloupka- painter were painting inside of home- need to reschedule
|
Final | 2/21/2018 | 2/22/2018 | 2/22/2018 | A | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka
|
Rough-in | 2/21/2018 | 2/22/2018 | 2/22/2018 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- R/I ok
|
Rough-in | 2/20/2018 | 2/21/2018 | 2/21/2018 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- need to insulate trasnsition between coil and furnace-draft stop at 2nd floor ceiling needs instaaled so insulation cant fall into chase- fix rips and tears on armaflex in wall 2nd floor- left correction notice front door window
|
Pressure Test | 2/20/2018 | 2/21/2018 | 2/21/2018 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- 20lb gas pass
|
Issue PAID IN FULL permit | | | 1/24/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/23/2018 | | DONE |
|
|
|
This permit was created on the web by Debbie Marino
|