Final | 6/15/2018 | 6/15/2018 | 6/15/2018 | P | PASS |
Brian Scoles
|
|
|
Front door is unlocked:) thanks Phone #: ###-#### Inspection requested via web by Gary Reeves- final ok
|
Final | 6/14/2018 | 6/15/2018 | 6/15/2018 | A | FAIL |
Brian Scoles
|
|
|
The front door will be open. Thanks Phone #: ###-#### Inspection requested via web by Gary Reeves- need uv proecion on lineset a a/c- a/c needs low voltage hooked up- missing register
|
Final | 6/12/2018 | 6/13/2018 | 6/12/2018 | P | CANC |
Brian Scoles
|
|
|
Front door and garage door is open for inspector to access the house, thanks Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves
|
Pressure Test | 6/4/2018 | 6/4/2018 | 6/4/2018 | P | PASS |
Brian Scoles
|
|
|
Please Inspect underground gas line. thanks Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb underground pass- ok for backfill
|
Rough-in | 3/1/2018 | 3/1/2018 | 3/1/2018 | P | PASS |
Brian Scoles
|
|
|
had to go tag gas line- all stickers were removed from window stating R/I and 20lb gas pass on it- talked to builder about this
|
Rough-in | 2/15/2018 | 2/16/2018 | 2/16/2018 | A | PASS |
Brian Scoles
|
|
|
access code is 9111 Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok- corrections made
|
Pressure Test | 2/15/2018 | 2/16/2018 | 2/16/2018 | A | PASS |
Brian Scoles
|
|
|
access code is 9111 Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pass
|
Pressure Test | 2/14/2018 | 2/15/2018 | 2/15/2018 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- gates locked up no access
|
Rough-in | 2/14/2018 | 2/15/2018 | 2/15/2018 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- gates locked up- reinspection fee issued for multiple inspections
|
Rough-in | 2/12/2018 | 2/13/2018 | 2/13/2018 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- dryer vent exceeds 35 feet max with all fittings reroute or use booster fan- utility room missing supply register its in pantry- R/A register not in location of per ACCA report check location if no door is in mud room will be ok- gas test fail- need nail plate on linset in wall of garage- need to fix all rips and tears and missing armaflex o n lineset from furnace to outside location- left correction notice by furnace
|
Pressure Test | 2/12/2018 | 2/13/2018 | 2/13/2018 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- gas pressure at 13 psi
|
Pressure Test | 2/5/2018 | 2/6/2018 | 2/6/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- no access gates locked up
|
Rough-in | 2/5/2018 | 2/6/2018 | 2/6/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- no access gates locked up in front of house- need access
|
Rough-in | 2/2/2018 | 2/5/2018 | 2/5/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- need approved ACCA report onsite to do inspection
|
Pressure Test | 2/2/2018 | 2/5/2018 | 2/5/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- guage doesnt zero out
|
Issue PAID IN FULL permit | | | 2/2/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/2/2018 | | DONE |
|
|
|
This permit was created on the web by Gary Reeves
|