Final | 6/19/2018 | 6/20/2018 | 6/20/2018 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss- FINAL OK
|
Final | 5/25/2018 | 5/29/2018 | 5/25/2018 | A | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Krista Boss Inspection cancelled from web by: Krista Boss
|
Final | 5/24/2018 | 5/25/2018 | 5/25/2018 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss- need to seal gas line penetration into crawl- need airbalance report onsite- need 3 screws in flue at water heater to china cap- need 2.25" from front of furnace to combustibles per manufactures installation manual( talked to Jason builder onsite about this)
|
Rough-in | 3/19/2018 | 3/19/2018 | 3/19/2018 | P | PASS |
Bill VanDegrift
|
|
|
|
Rough-in | 3/16/2018 | 3/16/2018 | 3/16/2018 | P | PART |
Brian Scoles
|
|
|
Daniel promises it is ready ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- R/I will pass for cover when all permits have been attached to right address
|
Rough-in | 3/15/2018 | 3/15/2018 | 3/15/2018 | P | NR |
Bill VanDegrift
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss framing corrections at furnace not made according to contractor.
|
Conference | 3/14/2018 | 3/14/2018 | 3/15/2018 | P | CANC |
Bill VanDegrift
|
|
|
this was just to investigate addressing and inspection issues
|
Rough-in | 3/14/2018 | 3/14/2018 | 3/14/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss- need approved ACCA report onsite for inspection- need right address on housing before next inspection
|
Rough-in | 2/28/2018 | 2/28/2018 | 2/28/2018 | P | NR |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss- still installing
|
Pressure Test | 2/28/2018 | 2/28/2018 | 2/28/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss- 20lb gas pass
|
Issue PAID IN FULL permit | | | 2/13/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/13/2018 | | DONE |
|
|
|
This permit was created on the web by Krista Boss
|