Final | 5/16/2018 | 5/16/2018 | 5/16/2018 | P | PASS |
Brian Scoles
|
|
|
final ok
|
Final | 5/7/2018 | 5/8/2018 | 5/8/2018 | A | FAIL |
Brian Scoles
|
|
|
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- needs drip leg on gas line between shutoff valve and appliance furnace and w/h- need airbalance report onsite
|
Rough-in | 3/22/2018 | 3/23/2018 | 3/23/2018 | P | PASS |
Brian Scoles
|
|
|
re-inspect Phone #: ###-#### Inspection requested via web by Brandon Sorensen- R/I ok
|
Rough-in | 3/21/2018 | 3/22/2018 | 3/22/2018 | P | FAIL |
Brian Scoles
|
|
|
Rough in - call david Phone #: ###-#### Inspection requested via web by Brandon Sorensen- supply ducting in garage needs to be R-8 unconditioned space- need to insulate wye branch in garage space ceiling level unconditioned space- need to insulate R/A between joist space in garage above furnace- correction notice on furnace
|
Pressure Test | 3/21/2018 | 3/22/2018 | 3/22/2018 | P | PASS |
Brian Scoles
|
|
|
pressure test - call david Phone #: ###-#### Inspection requested via web by Brandon Sorensen- 20lb gas pass
|
Issue PAID IN FULL permit | | | 3/12/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/12/2018 | | DONE |
|
|
|
This permit was created on the web by Brandon Sorensen
|