Permit Information
Permit NumberMEC18-01668
StatusFinaled
Name THOMAS HEATING & COOLING LLC
Site Address 935 E PARKCENTER BLVD
Project NameAmore Nail Studio TI
Customer Number 
ePlanReviewNo
Description
permit to add 3 duct systems and ventilation for 4 new nail stations
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/10/20187/11/20187/11/2018APASS
DetailsJack Reynolds
please call half hour prio Phone #: ###-#### Inspection requested via web by thomas nguyen- air balance report with new exhaust fans was emailed and ok- final ok
Final6/26/20186/26/20186/26/2018PPART
DetailsJack Reynolds
partial final with air balance report/ email stating when exhaust fans will be worked on and rebalanced/ extend flue on rtu up 3' above economizer - email of when new exhaust fans will be in place ok- air balance of exhaust systems at current state - EF 1 and EF 2 are below 80% and will need to be rebalanced for complete final- snorkel flue 3' above economizer ok
Final6/25/20186/26/20186/26/2018ANR
DetailsJack Reynolds
please call half prio Phone #: ###-#### Inspection requested via web by thomas nguyen
-scheduled a pm inspection- waiting on information and a fews things to be fixed by this afternoon
Final6/25/20186/25/20186/25/2018PNR
DetailsJack Reynolds
Thomas Phone #: ###-####- need to see air balance report on all nail stations for final
Rough-in6/18/20186/18/20186/18/2018PPASS
DetailsJack Reynolds
ceiling ducting, please call 30 mins ahead - Tom Phone #: ###-####- ceiling tile cover ok- need balance dampers at each branch on exhaust for nail stations
Rough-in4/28/20184/30/20184/30/2018APART
DetailsJack Reynolds
please call half hour prio Phone #: ###-#### Inspection requested via web by thomas nguyen- Exhaust duct work above hard lid for nail stations and framing for access door R/I ok- still need to see bathroom exhaust fan mounted in ceiling before cover
Rough-in4/27/20184/27/20184/27/2018PFAIL
DetailsJack Reynolds
please call half hour prio Phone #: ###-#### Inspection requested via web by thomas nguyen- seal all joints on nail station exhaust system above hard lid- also need access door framing in hard lid for eletric backdraft damper on south side for foot station
Rough-in4/24/20184/24/20184/24/2018PPART
DetailsJack Reynolds
please call half hour prio Phone #: ###-#### Inspection requested via web by thomas nguyen- ductwork seal checked and ok for duct insulation
Conference4/13/20184/16/20184/16/2018ADONE
DetailsChad Schwendiman
Please call ahead for access - Thomas Phone #: ###-#### - Discussed routing of duct work for the rtu in the back of the space, and insulation requirements
Application received  4/13/2018  
Issue PAID IN FULL permit  4/13/2018 DONE
First Notice7/11/20187/11/2018   
DetailsJack Reynolds