Permit NumberMEC18-01799
StatusFinaled
Name TVR INC
Site Address 2622 N COOLWATER AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: split system, ductwork, grd''s, exhaust and flue venting, t-stat
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/8/20188/8/20188/8/2018PPASS
DetailsBrian Scoles
final - call dave with any questions Phone #: ###-#### Inspection requested via web by Brandon Sorensen- final ok
Final7/24/20187/25/20187/25/2018AFAIL
DetailsBrian Scoles
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- no duct blast test done- water flue issues not addressed- corrections not made
Final7/18/20187/18/20187/18/2018PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Brandon Sorensen- need duct blast test done- need to replace flex b vent on water heater remove screws that were installed at ceiling to hold into place(not locked into place)and install per manufactures installation manual
Rough-in4/24/20184/25/20184/25/2018APASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Brandon Sorensen- R/I ok
Pressure Test4/24/20184/25/20184/25/2018APASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Brandon Sorensen- 20lb gas pass
Issue PAID IN FULL permit  4/23/2018 DONE
Payment received via Govolutions
Application received  4/23/2018 DONE
This permit was created on the web by Brandon Sorensen