Final | 12/12/2018 | 12/13/2018 | 12/13/2018 | P | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN per direction from engineering team to address condensate problem, heat pumps are for cooling only and will heat from internal heat strip.
|
Final | 11/13/2018 | 11/13/2018 | 11/13/2018 | P | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSENarmaflex needs uv protection, need 2nd condensate drain ran, not all units have balance report
|
Rough-in | 5/3/2018 | 5/4/2018 | 5/4/2018 | A | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
|
Issue PAID IN FULL permit | | | 5/3/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/3/2018 | | DONE |
|
|
|
This permit was created on the web by GREGORY ANDERSEN
|