Final | 7/26/2018 | 7/26/2018 | 7/26/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- final ok
|
Final | 7/26/2018 | 7/27/2018 | 7/26/2018 | A | CANC |
Brian Scoles
|
|
|
Final Garage Code 2468 Phone #: ###-#### >> Inspection requested via web by Randy Hart Inspection cancelled from web by: Randy Hart
|
Final | 7/24/2018 | 7/25/2018 | 7/25/2018 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- condensate still has trap running up hill- still need approved manual J onsite
|
Final | 7/5/2018 | 7/6/2018 | 7/6/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- primary drain is trapped off coil needs 1/4" per foo slope to drain and 90 degree glued at drain- need approved manual J onsite for inspection couldnt find one
|
Conference | 5/29/2018 | 5/29/2018 | 5/29/2018 | A | PASS |
Brian Scoles
|
|
|
Blast witness at 10 please Phone #: ###-#### Inspection requested via web by Randy Hart- duct blast test pas
|
Rough-in | 5/16/2018 | 5/17/2018 | 5/17/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- R/I ok
|
Rough-in | 5/16/2018 | 5/16/2018 | 5/16/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- need approved ACCA report onsite for inspection- need all insulation remove to do inspection- left do not cover sticker front window
|
Pressure Test | 5/16/2018 | 5/16/2018 | 5/16/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass
|
Issue PAID IN FULL permit | | | 5/14/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/14/2018 | | DONE |
|
|
|
This permit was created on the web by Randy Hart
|