Final | 7/2/2018 | 7/3/2018 | 7/3/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- final ok
|
Final | 6/28/2018 | 7/2/2018 | 7/2/2018 | P | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- line set has rips that need fixed with tape- line set needs UV protection- ductblast ok- airbalance report ok- Man J. and outdoor unit match
|
Conference | 5/29/2018 | 5/30/2018 | 5/30/2018 | A | PASS |
Brian Scoles
|
|
|
Blast witness at 9:30 Please Phone #: ###-#### Inspection requested via web by Randy Hart- duct blast test pass
|
Rough-in | 5/18/2018 | 5/21/2018 | 5/21/2018 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- R/I ok
|
Rough-in | 5/16/2018 | 5/17/2018 | 5/17/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- need transfer grill for bedroom #4- rest is good
|
Rough-in | 5/15/2018 | 5/16/2018 | 5/16/2018 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- need approved ACCA report onsite- need to fix all rips and tears in arma flex- gas piping needs to be secured to support in garage- b vent needs 1" clearance to combustibles at roof on water heater flue
|
Pressure Test | 5/15/2018 | 5/16/2018 | 5/16/2018 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass
|
Issue PAID IN FULL permit | | | 5/14/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/14/2018 | | DONE |
|
|
|
This permit was created on the web by Randy Hart
|