Final | 1/31/2019 | 1/31/2019 | 1/31/2019 | P | PASS |
Ben Livingston
|
|
|
Request for Final NR still showing on previous requests. If possible can we get in early afternoon. System at 7:26 am this morning would not let me schedule AM inspection for today. Inspection requested via web by Heather Gransbery
|
Final | 1/28/2019 | 1/28/2019 | 1/28/2019 | P | NR |
Ben Livingston
|
|
|
Request for PM inspection Final for TCO Inspection requested via web by Heather Gransbery
|
Final | 1/25/2019 | 1/25/2019 | 1/25/2019 | P | NR |
Ben Livingston
|
|
|
Heather Phone #: ###-#### fire suppression system on kitchen hood needs to be working for TCO
|
Final | 1/24/2019 | 1/24/2019 | 1/24/2019 | P | NR |
Ben Livingston
|
|
|
Request for Final inspection. Please contact Rob with any questions or concerns ###-#### Inspection requested via web by Heather Gransbery label FSD access doors, uv tape on line sets,remove inner ring on dryer exhaust outlet,
|
Rough-in | 1/11/2019 | 1/11/2019 | 1/11/2019 | P | PART |
Eric Strole
|
|
|
request for above ceiling cover inspection in Kitchen. Please contact Rob ###-#### with any questions or concerns. Inspection requested via web by Heather Gransbery-Insulation pass, ok to install grid.
|
Final | 1/7/2019 | 1/8/2019 | 1/8/2019 | A | FAIL |
Eric Strole
|
|
|
Request for final inspection for Bld D and C, not including the kitchen area. Please contact Rob ###-#### with any questions or concerns. Inspection requested via web by Heather Gransbery-No temp finals till a temp final plan is worked out with the city.
|
Rough-in | 1/3/2019 | 1/3/2019 | 1/3/2019 | A | PART |
Eric Strole
|
|
|
request for duct sealing inspection for the kitchen in BLD C Please contact Rob ###-#### with any questions or concerns. Inspection requested via web by Heather Gransbery-Main trunk in kitchen duct seal pass.
|
Rough-in | 12/7/2018 | 12/7/2018 | 12/7/2018 | P | PASS |
Chad Schwendiman
|
|
|
Request for insulation inspection on grease duct and inspection on Laundry Room C. Please contact Rob with any questions or concerns. ###-#### Inspection requested via web by Heather Gransbery - grease wrap okay. Laundry room okay to cover
|
Rough-in | 12/7/2018 | 12/7/2018 | 12/7/2018 | P | CANC |
Eric Strole
|
|
|
Request for inspection on insulation on grease duct in Kitchen. Please contact Rob ###-#### with concerns or questions. >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
|
Rough-in | 12/6/2018 | 12/6/2018 | 12/6/2018 | P | PASS |
Chad Schwendiman
|
|
|
Request for light test BLD D Kitchen. Please contact Rob ###-#### with any questions. Inspection requested via web by Heather Gransbery
|
Rough-in | 12/4/2018 | 12/5/2018 | 12/5/2018 | A | FAIL |
Chad Schwendiman
|
|
|
Request for light test in kitchen. Please contact Rob ###-#### or Casey ###-#### with any questions or concerns. Inspection requested via web by Heather Gransbery - Grease duct light test fail at hood connection
|
Rough-in | 12/4/2018 | 12/4/2018 | 12/4/2018 | A | PASS |
Chad Schwendiman
|
|
|
Request for inspection on Kitchen...fire dampers. Please contact Rob with any questions or concerns ###-#### Inspection requested via web by Heather Gransbery - Okay to sheetrock kitchen
|
Rough-in | 11/29/2018 | 11/30/2018 | 11/30/2018 | A | FAIL |
Chad Schwendiman
|
|
|
Request for R/I inspection for Kitchen. Please contact Rob ###-#### with any questions or concerns Inspection requested via web by Heather Gransbery - Need manufactures installation instructions for Fire damper framing in wood framed walls
|
Rough-in | 11/26/2018 | 11/26/2018 | 11/26/2018 | A | PASS |
Chad Schwendiman
|
|
|
Request for inspection on 2nd layer grease duct in Kitchen. Please contact Rob w/ any questions or concerns ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 11/17/2018 | 11/19/2018 | 11/19/2018 | A | PASS |
Chad Schwendiman
|
|
|
Request for inspection on first layer wrap in kitchen BLD D. Please contact Casey ###-#### or Rob ###-#### with any questions or concerns. Inspection requested via web by Heather Gransbery - 1st layer okay
|
Rough-in | 11/15/2018 | 11/16/2018 | 11/16/2018 | P | PASS |
Ben Livingston
|
|
|
Request for light test inspection in Kitchen BLD C/D. Please contact Mike ###-#### or Rob ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery 1-10' duct with 2 90s, 1-6'drop, light test
|
Rough-in | 11/6/2018 | 11/7/2018 | 11/7/2018 | A | PART |
Jack Reynolds
|
|
|
Request for inspection on partial kitchen. Building C/D. Please contact Rob with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - 2 dampers in back of kitchen next to walk in cooler one 8" and one 12" clearances ok. will call in for angle inspection tomorrow
|
Rough-in | 9/18/2018 | 9/19/2018 | 9/19/2018 | P | PASS |
Ben Livingston
|
|
|
Angle for fire dampers C ; D. Call Rob with any questions ###-####. Phone #: ###-#### Inspection requested via web by Bailey Esposito angles on dampers C,D corridors
|
Rough-in | 9/17/2018 | 9/18/2018 | 9/18/2018 | P | FAIL |
Ben Livingston
|
|
|
request for FD inspection in Building C. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery duct in corridors C,D okay and duct seal, FD angles not installed per manufactures instruction
|
Rough-in | 9/17/2018 | 9/17/2018 | 9/17/2018 | P | PASS |
Ben Livingston
|
|
|
Request for R/I fire smoke dampers Bld D to Bld C. Please contact Rob with any questions or concerns ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery 4 fire/smoke damper clearances hallway C,D
|
Rough-in | 9/13/2018 | 9/13/2018 | 9/13/2018 | A | CANC |
Ben Livingston
|
|
|
Request for R/I fire smoke dampers Bld D to Bld C. Please contact Rob with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Rough-in | 9/12/2018 | 9/13/2018 | 9/13/2018 | A | FAIL |
Eric Strole
|
|
|
Request for R/I fire smoke dampers Bld D to Bld C. Please contact Rob with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery-Need to install fire/smoke dampers per manufacture installation instructions.
|
Rough-in | 9/10/2018 | 9/11/2018 | 9/11/2018 | A | PART |
Jack Reynolds
|
|
|
Request above ceiling Bld C and Connect area duct seal inspection C ; D. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - duct seal for connect area from D to C on NW side ok- bldC common area insulation ok up to gridline 3.4 cover ok -bldC south and west corridors insulation ok
|
Rough-in | 9/5/2018 | 9/5/2018 | 9/5/2018 | P | PASS |
Ben Livingston
|
|
|
room 101 duct seal okay
|
Rough-in | 9/5/2018 | 9/5/2018 | 9/5/2018 | A | PART |
Eric Strole
|
|
|
Request for duct seal inspection RTU #1 in Bld C Common Area. Please contact Rob with questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery-RTU #1 common area ok to insulate.
|
Rough-in | 8/30/2018 | 8/31/2018 | 8/31/2018 | A | PASS |
Eric Strole
|
|
|
Request for duct seal inspection in bld c common area. Please contact Rob ###-#### w/ any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery-2nd 1/2 of RTU# 1 supply and return duct seal
|
Rough-in | 8/29/2018 | 8/30/2018 | 8/30/2018 | A | PASS |
Ben Livingston
|
|
|
Request for inspection on duct seal, common area Bld C. Please contact Rob with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery 1st 1/2 of RTU# 1 supply and return duct seal
|
Rough-in | 8/24/2018 | 8/24/2018 | 8/24/2018 | A | PART |
Eric Strole
|
|
|
inspection request for area C r/I rooms and common area. Please contact Rob ###-#### with any questions or concerns Phone #: ###-#### Inspection requested via web by Heather Gransbery-Rooms 102 through 112 duct insulation pass. Duct seal rtu # 3 system pass.
|
Rough-in | 8/20/2018 | 8/20/2018 | 8/20/2018 | P | PART |
Eric Strole
|
|
|
request for R/I inspection on Bld D. Rooms 136,129,127 . Please contact Rob with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery-Insulation cover in rooms 113,127,129,136 pass.
|
Rough-in | 8/15/2018 | 8/15/2018 | 8/15/2018 | A | PART |
Eric Strole
|
|
|
request for duct seal inspection for the rooms in area C. Please contact job lead, Rob, ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery-Duct seal area c west and south rooms pass.
|
Rough-in | 8/3/2018 | 8/6/2018 | 8/6/2018 | A | PART |
Ben Livingston
|
|
|
request for R/I inspection on Bld D. Please contact job lead Rob, ###-#### with any questions or concerns Phone #: ###-#### Inspection requested via web by Heather Gransbery all rooms in area D, rooms 136,129,127 still need insulation
|
Rough-in | 7/27/2018 | 7/30/2018 | 7/30/2018 | A | PASS |
Ben Livingston
|
|
|
request for inspection duct seal Bld C. Please contact job lead Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery main corridor area C supply and exhaust trunklines duct seal okay area B supply and exhaust duct insulation okay
|
Rough-in | 7/24/2018 | 7/25/2018 | 7/25/2018 | A | PASS |
Ben Livingston
|
|
|
Request for R/I duct seal inspection. Please contact job lead Rob with questions and concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery down spouts on bathrooms area D duct seal
|
Conference | 7/23/2018 | 7/23/2018 | 7/23/2018 | P | DONE |
Chad Schwendiman
|
|
|
Request for conference/consult. Please contact Rob with any questions or concerns. ###-#### Phone #: ###-#### Inspection - conference discussing fire damper access
|
Conference | 7/23/2018 | 7/23/2018 | 7/23/2018 | P | DONE |
Eric Strole
|
|
|
Request for conference/consult. Please contact Rob with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery-Conferance on access for fire/smoke dampers.
|
Conference | 7/23/2018 | 7/23/2018 | 7/23/2018 | P | PASS |
Ben Livingston
|
|
|
Request for conference/consult. Please contact Rob with any questions or concerns. ###-#### Phone #: ###-#### Inspection
|
Conference | 7/23/2018 | 7/23/2018 | 7/23/2018 | P | CANC |
Eric Strole
|
|
|
Request for conference/consult. Please contact Rob with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Conference | 7/18/2018 | 7/20/2018 | 7/20/2018 | A | PART |
Eric Strole
|
|
|
Request for r/I conference for Area D. Please contact Rob Campbell ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery-Duct seal in corridor pass. ok to insulate.
|
Conference | 7/19/2018 | 7/20/2018 | 7/20/2018 | A | PASS |
Ben Livingston
|
|
|
Request for r/I conference for Area D. Please contact Rob Campbell ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Issue PAID IN FULL permit | | | 5/16/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/16/2018 | | DONE |
|
|
|
This permit was created on the web by Heather Gransbery
|
First Notice | 1/31/2019 | 1/31/2019 | | | |
Ben Livingston
|
|
|
|