Final | 6/20/2019 | 6/21/2019 | 6/21/2019 | A | PASS |
Chad Schwendiman
|
|
|
Mechanical Final inspection needed for AM please call Karl with any questions at ###-#### thank you Phone #: ###-#### Inspection requested via web by Karl Hestekin
|
Final | 6/14/2019 | 6/17/2019 | 6/17/2019 | A | FAIL |
Brian Scoles
|
|
|
Mechanical Final Inspection needed for AM Monday please contact Karl with any questions thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin- correction not made in kitchen- roof ok
|
Final | 6/13/2019 | 6/14/2019 | 6/14/2019 | A | FAIL |
Chad Schwendiman
|
|
|
Final inspection needed for AM I will have the air balance report in the morning as soon as I get it I will send to Brian Scoles and Chad Schwendiman please contact Karl with any questions at ###-#### thank you Phone #: ###-#### Inspection requested via web by Karl Hestekin - Need out air filters installed an SF-1 & 2, Class 1 hoods need to over hang the appliances by 6" on all open sides
|
Rough-in | 4/22/2019 | 4/23/2019 | 4/23/2019 | A | CANC |
Brian Scoles
|
|
|
Rough-in inspection for Milwaukee Nail Salon Please contact Karl before going to project to ensure that door is unlocked thank you Phone #: ###-#### Inspection requested via web by Karl Hestekin
|
(F) Reprint permit | | | 2/26/2019 | | DONE |
|
|
|
|
(F) Reprint permit | | | 2/26/2019 | | DONE |
|
|
|
|
(F) Reprint permit | | | 2/26/2019 | | DONE |
|
|
|
|
Conference | 2/7/2019 | 2/7/2019 | 2/7/2019 | A | DONE |
Chad Schwendiman
|
|
|
Met onsite to discuss the existing class 1 hoods. The existing hoods are not being altered, and are being left as they were originally installed and approved for the previouse tenant. Because of this I agreed to let them remain as, but that they need to install stainless steel on all the wall sufaces within 18" of the hoods, and use noncombustable panels in the grid ceiling with in 18" of the hoods. I also advised that we will need an air balance report for the existing hoods using ther CFM's shown on the drawings
|
Conference | 2/6/2019 | 2/7/2019 | 2/7/2019 | A | DONE |
Brian Scoles
|
|
|
Conference AM for Magnificent Garden Please contact Karl with any questions thank you Phone #: ###-#### Inspection requested via web by Karl Hestekin- met with chad karl GC and went over kitchen area for clearance to combusibles issues with class 1 hoods- will install ss sheetmetal in all locations to bring to code
|
Conference | 2/6/2019 | 2/6/2019 | 2/6/2019 | P | DONE |
Brian Scoles
|
|
|
Need a conference for Magnificent Garden by phone today at 1:00pm if possible can contact Karl at ###-#### thank you Phone #: ###-#### Inspection requested via web by Karl Hestekin- looked at existing hoods in kitchen where walls and ceiling were replaced- wasnt on prints of any work done to kitchen area- clearance to combustibles might not be met- all labeling is gone or not ledgeable- will meet tomorrow with chad and karl at 930ish
|
Rough-in | 1/11/2019 | 1/14/2019 | 1/14/2019 | A | PART |
Brian Scoles
|
|
|
2nd layer fire wrap needed for Magnificent Garden contact Rob with any questions ###-#### thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin- 2nd layer fire wrap ok- still need access door framing for all grease duct installed before cover can be issued- need installation instructions on owner provided equipment being installed
|
Rough-in | 1/4/2019 | 1/7/2019 | 1/7/2019 | A | PART |
Brian Scoles
|
|
|
Mechanical 2nd Layer Fire wrap needed for Magnificent Garden if you have questions call Karl at ###-#### thank you Phone #: ###-#### Inspection requested via web by Karl Hestekin- missing a couple access doors still- need to add insulation straps on all 90s in throat to heal of 90s and a few places are farther than 12" apart- still need installation instruction on owner provided equipment to verify access doors need to have gasket/sealing meeting 1500 degrees
|
Rough-in | 11/12/2018 | 11/13/2018 | 11/13/2018 | A | PART |
Brian Scoles
|
|
|
Mechanical 1st layer fire wrap inspection am preferred please contact Rob at ###-#### thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin- 1st layer firewrap ok- ok for 2nd layer- middle exhaust west side missing 1 access door on order- still need installation instruction manual on owner provided equipment
|
Rough-in | 11/6/2018 | 11/7/2018 | 11/7/2018 | A | PART |
Brian Scoles
|
|
|
Mechanical Grease Duct Inspection needed for Magnificent Garden Am preferred if you have any questions contact Rob at ###-####167 thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin- Grease duct light test all custom made ducts ok for 1st layer of fire wrap- need installation instruction on grease boxes provide by owner
|
Rough-in | 11/2/2018 | 11/5/2018 | 11/5/2018 | A | PART |
Brian Scoles
|
|
|
Mechanical Grease Duct Inspection Needed For Monday AM Please Contact Rob At ###-####. Phone #: ###-#### Inspection requested via web by Karl Hestekin- still have at least 10 holes that need addressed
|
Rough-in | 10/26/2018 | 10/29/2018 | 10/29/2018 | A | FAIL |
Brian Scoles
|
|
|
A.M. Mechanical Grease duct inspection needed contact Rob with any questions. thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin- checked all square grease duct to many holes-
|
Rough-in | 10/24/2018 | 10/26/2018 | 10/26/2018 | A | PART |
Brian Scoles
|
|
|
Am Mechanical grease duct inspection for Magnificent Garden, if you have questions contact Rob at ###-####, thank you:) Phone #: ###-#### Inspection requested via web by Karl Hestekin- checked a couple runs and found some pin holes- Rob will build a shelter to do rest of light test to bright in room- will reschedule for monday
|
Rough-in | 9/4/2018 | 9/5/2018 | 9/5/2018 | A | PASS |
Brian Scoles
|
|
|
Mechanical Partial Grease Duct Inspection needed for Magnificent Garden please contact Rob with any questions at ###-#### Thank you:) Phone #: ###-#### Inspection requested via web by Karl Hestekin- missing few bands to complete horizontal mains- ok to insulate horizontal lines excluding tap locations-
|
Rough-in | 8/24/2018 | 8/24/2018 | 8/24/2018 | P | CANC |
Brian Scoles
|
|
|
Rough-In inspection needed for Magnificent Garden please contact Mike with any questions.###-#### Phone #: ###-#### >> Inspection requested via web by Karl Hestekin Inspection cancelled from web by: Karl Hestekin
|
Rough-in | 8/22/2018 | 8/23/2018 | 8/23/2018 | A | PART |
Brian Scoles
|
|
|
Rough in needed for AM at Magnificent Garden Also need a partial grease duct inspection contact Rob at ###-#### before you go to job site thanks Phone #: ###-#### Inspection requested via web by Karl Hestekin- 7 grease duct drops ok to firewrap- ok to cover registers- seal on duct ok- need to install clean out access doors and finish grease duct- no cover on horizontal chases a this time
|
Conference | 7/23/2018 | 7/24/2018 | 7/24/2018 | A | DONE |
Brian Scoles
|
|
|
Conference needed at 11:00 am please call Karl with any questions at 208 401 5600 thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin- discussed mock up and gas piping and fire protection location on duct or ansl system-
|
Conference | 7/19/2018 | 7/19/2018 | 7/19/2018 | P | DONE |
Troy James
|
|
|
Meeting with architects and contractors at 2:00pm mechanical contractor will do a mockup at table where two grease ducts come together
|
Conference | 7/19/2018 | 7/19/2018 | 7/19/2018 | P | CANC |
Brian Scoles
|
|
|
at 200pm meet with Troy- Discussed issues forgrease duct serving 2 tables- Karl will make mock up and meet again-
|
Conference | 5/17/2018 | 5/21/2018 | 5/21/2018 | A | DONE |
Brian Scoles
|
|
|
Can you please schedule a conference for 10 A.M. Monday for the Magnificent Garden in Boise. Meeting will be held at the following. Thanks If you need to speak to Karl prior to the conference please call ###-####.
Monday May 21, 2018 @ 10am Musgrove Engineering 234 S. Whisperwood Way Boise, Idaho Phone #: ###-#### Inspection requested via web by Karl Hestekin-- discussion of location on reserviors on ducting and height issues- will have grease reservior in middle of duct with pitch each way back to reservior
|
Conference | 5/17/2018 | 5/21/2018 | 5/21/2018 | A | DONE |
Chad Schwendiman
|
|
|
Meet to discuss clean out locations and reservoir locations for greas duct
|
Conference | 5/17/2018 | 5/17/2018 | 5/17/2018 | A | CANC |
Chad Schwendiman
|
|
|
10 am
|
Issue PAID IN FULL permit | | | 5/17/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/17/2018 | | DONE |
|
|
|
This permit was created on the web by Karl Hestekin
|
Telephone call | | | 5/17/2018 | | DONE |
|
|
|
call for inspectors phone number
|
First Notice | 6/21/2019 | 6/21/2019 | | | |
Chad Schwendiman
|
|
|
|