Final | 9/4/2018 | 9/5/2018 | 9/5/2018 | A | PASS |
Jack Reynolds
|
|
|
Jonny Phone #: ###-####
|
Final | 8/28/2018 | 8/29/2018 | 8/29/2018 | A | FAIL |
Jack Reynolds
|
|
|
if no body there call for access // Jonny Phone #: ###-#### - furnace in basement needs a wet switchh installed in the secoundary- condensate drain for heating side of furnace is not ran- need to finish duct seal- upstairs furnace needs lineset insulation fixed- need drip leg in gas line- need to finish duct seal- kitcken exhaust ok
|
Pressure Test | 8/1/2018 | 8/1/2018 | 8/1/2018 | P | PASS |
Chad Schwendiman
|
|
|
5lb flue
|
Final | 7/30/2018 | 7/31/2018 | 7/31/2018 | A | CANC |
Jack Reynolds
|
|
|
(gas/range)- Johnny Phone #: ###-#### should have been a R/I for the range- i also need to see a 5lb flue test on upstairs furnace still
|
Rough-in | 7/31/2018 | 7/31/2018 | 7/31/2018 | P | PASS |
Jack Reynolds
|
|
|
(gas/range)- Johnny Phone #: ###-#### R/I ok on range
|
Rough-in | 6/12/2018 | 6/13/2018 | 6/13/2018 | A | PASS |
Chad Schwendiman
|
|
|
johnny Phone #: ###-#### - No range vent installed at this time
|
Pressure Test | 5/30/2018 | 5/31/2018 | 5/31/2018 | A | PART |
Chad Schwendiman
|
|
|
Johnny-- gas pressure test- are 2 furnaces, need to pay for other one Phone #: ###-#### - 5lb flue fail for upstairs furnace, 5lb flue pass for furnace in basement, 20lb gas pass
|
(F) Reprint permit | | | 5/30/2018 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 5/17/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/17/2018 | | DONE |
|
|
|
This permit was created on the web by johnny frank
|