Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberMEC18-02294
StatusFinaled
Name PAIGE MECHANICAL GROUP INC
Site Address 1757 N HAMPTON RD
Project Name 
Customer Number18.7029.23
ePlanReviewNo
Description
Alteration: Install Mechanical Equipment, Duct, Trim, and Controls
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Print Statement  10/1/2018 DONE
Final7/16/20187/16/20187/16/2018PPASS
DetailsBrian Scoles
final ok
Final7/9/20187/10/20187/10/2018AFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Nicholas Paige- PVC and ABS piping needs to be covered with plenum rated material, pipe insulation is not a rated assembly- plumbing inspector will take care of this on his permit when called in for inspection- flex to registers ok- no ceiling tiles until this inspection passes
Rough-in6/7/20186/8/20186/8/2018APART
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Nicholas Paige- need o add 10x10 transfer grills upsair op all rooms except bahroom- insulaion in walls main level needs return air paths for plenum return- pvc in plenum space needs fire wrap or blocked off- ok for grid
Rough-in5/22/20185/23/20185/23/2018APART
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Nicholas Paige- R/i and seal ok- ok to cover hard lids, chase around duct and dryer vents only
Issue PAID IN FULL permit  5/22/2018 DONE
Payment received via Govolutions
Application received  5/22/2018 DONE
This permit was created on the web by Nicholas Paige
First Notice7/16/20187/16/2018   
DetailsBrian Scoles