Permit Information
Permit NumberMEC18-02755
StatusFinaled
Name A-1 HEATING & AIR CONDITIONING
Site Address 7402 W FAIRVIEW AVE
Project Name 
Customer NumberCVS
ePlanReviewNo
Description
Alteration: Install 4 rooftop unit heaters, the gas piping is being done by others. Vent two bath fans. Install a single port minisplit system. Ductwork. Install and vent a unit heater. N2180301-9----8-13-18 C=Krista called adding to permit-also doing all the refrigeration
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/28/201810/1/201810/1/2018PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Krista Boss- final ok
Final9/26/201810/1/20189/27/2018ACANC
DetailsBrian Scoles
Phone #: ###-#### >> Inspection requested via web by Krista Boss Inspection cancelled from web by: Krista Boss
Rough-in9/12/20189/13/20189/13/2018APASS
DetailsBrian Scoles
Lay in grid. Aleks ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- R/A grills ok- ok for remaining cwiling tiles to be installed
Rough-in8/30/20188/31/20188/31/2018APASS
DetailsChad Schwendiman
lay in grid on RTU 1, 2, ; 3 Inspection requested via web by Krista Boss- final ok Phone #: ###-#### - Okay to cover grid ceilings except for around return grills. Ceiling tiles around return grills are to be left out for inspection once completed
Rough-in8/29/20188/31/20188/30/2018ACANC
DetailsBrian Scoles
lay in grid on RTU 1, 2, ; 3 Phone #: ###-#### Inspection requested via web by Krista Boss-
CHANGE STATUS TO (ISS)  8/30/2018 DONE
Some how final when passed on rough-in inspection. Per Brian
Rough-in8/13/20188/13/20188/13/2018PPASS
DetailsBrian Scoles
refrigeration Phone #: ###-#### Inspection requested via web by Krista Boss- R/I ok on refridgeration lines- ok for grid to be installed
Rough-in8/9/20188/9/20188/9/2018PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Krista Boss- R/I ok- will look at seal and hangers on final-ok for ceiling grid
Rough-in8/7/20188/7/20188/7/2018PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Krista Boss- need to fix all rips and tears in arma flex and support lineset for manager office- seal on duct south east corner needs sealed better off RTU 1- all ducting above grid needs insulated per M$ detail 6 and 7 excluding rooms under mezz- R/A drops di not match prints need to get engineers approval on whats installed- unit heater 1 needs installed per detal and length is pretty long? can not support to duct work- left correction notice with general and went over these issues
Rough-in7/10/20187/11/20187/11/2018APART
DetailsChad Schwendiman
please call Aleks - part r/i on rtu 3 ;4 - ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss - Duct work okay for RTU's 3, and 4. Okay to cover ceilings and walls in back office area of building
Issue PAID IN FULL permit  6/14/2018 DONE
Payment received via Govolutions
Owner Supplied Equipment  6/13/2018  
Application received  6/13/2018 DONE
This permit was created on the web by Krista Boss
First Notice10/1/201810/1/2018   
DetailsBrian Scoles