Final | 9/25/2018 | 9/26/2018 | 9/26/2018 | A | PASS |
Brian Scoles
|
|
|
Code 0316.manual j ; air balance report onsite. Phone #: ###-#### Inspection requested via web by Angie Thome- final ok
|
Final | 9/23/2018 | 9/24/2018 | 9/24/2018 | A | FAIL |
Brian Scoles
|
|
|
Code 0316 Manual J onsite. Phone #: ###-#### Inspection requested via web by Angie Thome- need uv protection on linset out side at a/c- tape up rips and tears on arma flex at coil location- need airbalance report onsite couldnt find one- no meter yet
|
Rough-in | 6/26/2018 | 6/27/2018 | 6/27/2018 | A | PASS |
Brian Scoles
|
|
|
Man J is in a white pvc tube marked plans. Usually near the furnace. Phone #: ###-#### Inspection requested via web by Angie Thome- R/I ok
|
Rough-in | 6/25/2018 | 6/26/2018 | 6/26/2018 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Angie Thome- need nail plate on dryer exhaust in closet at floor level- R/I ok except for missing nail plate
|
Pressure Test | 6/21/2018 | 6/22/2018 | 6/22/2018 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Angie Thome - 20lb gas pass
|
Rough-in | 6/21/2018 | 6/22/2018 | 6/22/2018 | P | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Angie Thome - 1) Need approved manual J onsite 2) Fresh air duct can not come from the roof 3) Need a minimum of 4" wide framing on wall with dryer duct so duct isn't smashed 4) Missing nail plates on dryer duct
|
Rough-in | 6/21/2018 | 6/22/2018 | 6/21/2018 | A | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Angie Thome Inspection cancelled from web by: Angie Thome
|
Issue PAID IN FULL permit | | | 6/21/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/21/2018 | | DONE |
|
|
|
This permit was created on the web by Angie Thome
|