Permit Information
Permit NumberMEC18-02995
StatusFinaled
Name A-1 HEATING & AIR CONDITIONING
Site Address 7920 W MAXWELL DR
Project Name 
Customer NumberThompson
ePlanReviewNo
Description
Complete HVAC Installation: Install furnace and AC. Gas pipe to furnace, water heater, fire place, and range. Vent range, dryer, and 4 bath fans.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/30/20188/30/20188/30/2018PPASS
DetailsBrian Scoles
final ok
Final8/30/20188/30/20188/30/2018PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Krista Boss- water heater flue still needs 3 screw where b vent ties onto single wall pipe- need to support primary condesate drain off coil for protection to damage-
Final8/28/20188/29/20188/29/2018PFAIL
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Krista Boss- furnace condensate drain needs pumpoed to washer box or to approved location- primary drain in coil needs ran to approved location- condenser pad needs to be flush with outside of condenser(over hangs) or bigger pad for protection to equipment- water flue needs 3 screws in flue joints- left correction notice on furnace door
Rough-in7/11/20187/12/20187/12/2018ACANC
DetailsBrian Scoles
Phone #: ###-#### >> Inspection requested via web by Krista Boss Inspection cancelled from web by: Krista Boss
Rough-in7/11/20187/11/20187/11/2018PPASS
DetailsChad Schwendiman
Pressure Test7/11/20187/11/20187/11/2018PPASS
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Krista Boss - 20lb gas pass 5lb flue pass
Rough-in7/11/20187/11/20187/11/2018PFAIL
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Krista Boss - Need a copy of the approved manual J onsite.
Pressure Test7/10/20187/11/20187/11/2018AFAIL
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Krista Boss - gas pressure fail, flue pressure fail
Rough-in7/10/20187/11/20187/11/2018AFAIL
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Krista Boss -
1) Need approved manual J onsite
2) Need insulation shield on B-vent in attic
3) Need 1" clearance to combustables from B-vent. ( wires in attic)
4) Exhaust fans vents not connected
Issue PAID IN FULL permit  6/26/2018 DONE
Payment received via Govolutions
Application received  6/26/2018 DONE
This permit was created on the web by Krista Boss