Final | 3/19/2019 | 3/21/2019 | 3/21/2019 | A | PASS |
Jack Reynolds
|
|
|
please call Malisa when 30 mins in route. We left a ladder for you to access the attic access Phone #: ###-#### Inspection requested via web by Rick Montgomery - furnace ac coil co ok
|
Mec-Aging Inspection | 3/19/2019 | 3/19/2019 | 3/19/2019 | | DONE |
Jack Reynolds
|
|
|
Called Diamond Heating and talked with Steve about their mechanical aging permit. Schedule inspection with homeowner if correction have been made. Permit will expire within 180 days 8/19/18
|
Final | 8/29/2018 | 8/29/2018 | 8/29/2018 | P | FAIL |
Jack Reynolds
|
|
|
please call office 30 mins prior to arrival . We will make sure ladder is there for you to access attic Phone #: ###-#### Inspection requested via web by Rick Montgomery- this is the furnace above the visitor center - Common b vent needs 1" clearances- need a drip leg in gas line- wet switch needs to be sealed to pan or replace with a hockey puck style wet switch- need to reinstall refrigerant clamps at A/C
|
Issue PAID IN FULL permit | | | 6/27/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/27/2018 | | DONE |
|
|
|
This permit was created on the web by Rick Montgomery
|