Final | 9/18/2018 | 9/18/2018 | 9/18/2018 | P | PASS |
Brian Scoles
|
|
|
MEC AND FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak- final on hvac and fireplace ok
|
Pressure Test | 7/3/2018 | 7/3/2018 | 7/3/2018 | P | PASS |
Bill VanDegrift
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak ri fp 20# ok
|
Rough-in | 7/3/2018 | 7/3/2018 | 7/3/2018 | P | PASS |
Bill VanDegrift
|
|
|
MEC AND FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak ri fp 20# test ok
|
Rough-in | 6/28/2018 | 6/28/2018 | 6/28/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- insulation shield needs to be 1" cleance to bvent to small- need framing completed around b vent main level??? and firestop installed at ceiling- need access framed in for acces to furnace in attic or extend platform all the way to master closet access 24" wide minimum- R/A and supply air need to be insulated and secured- condensate needs nail plates and hangers installed- need make up air for range hood- coil and furnace do no match manual J on sizing and brand installed- left correction notice fron window
|
Pressure Test | 6/28/2018 | 6/28/2018 | 6/28/2018 | P | CANC |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass
|
Issue PAID IN FULL permit | | | 6/28/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/28/2018 | | DONE |
|
|
|
This permit was created on the web by Oleg Chervak
|