Final | 9/24/2018 | 9/25/2018 | 9/25/2018 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Brenda Baxter- final ok
|
Rough-in | 8/7/2018 | 8/8/2018 | 8/8/2018 | A | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Baxter- R/I ok- 20lb gas pressure test ok
|
Rough-in | 8/6/2018 | 8/6/2018 | 8/6/2018 | P | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Baxter - line set insulation has rips inside the wall and at the nail plate -supply flex runs have sharp 90 bends before boots( laundry room and hallway) -need to adjust several flex supports that are cutting off flex runs -no access to attic to check equipment -20lb gas pressure test OK
|
Fees Due Hold | 6/29/2018 | | 7/9/2018 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 6/28/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/28/2018 | | DONE |
|
|
|
This permit was created on the web by Jason Baxter
|