First Notice | 4/3/2019 | 4/3/2019 | 4/11/2019 | | DONE |
Brian Scoles
|
|
|
This permit finaled on the web by Stacia Haumann
|
Final | 4/3/2019 | 4/3/2019 | 4/3/2019 | P | PASS |
Brian Scoles
|
|
|
if questions call Omar @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann- final ok- no card onsite to sign
|
Card not on site to sign | 4/3/2019 | 4/3/2019 | 4/3/2019 | P | PASS |
Brian Scoles
|
|
|
if questions call Omar @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
|
Final | 4/2/2019 | 4/2/2019 | 4/2/2019 | P | PART |
Brian Scoles
|
|
|
if questions call Omar @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann- roof gas piping ok- fireplace piping needs to be hard piped or csst gas piping with sleeve thru appliance- appliance connectors can not penetrate thru appliance- recall in when ready went over with Omar onsite- IFGC 411.3.3
|
Mec-Aging Inspection | 3/25/2019 | 3/25/2019 | 3/25/2019 | | PASS |
Brian Scoles
|
|
|
WIP-
|
Pressure Test | 9/24/2018 | 9/24/2018 | 9/24/2018 | P | PASS |
Jack Reynolds
|
|
|
Gas Line - Pressure Test. If questions call Omar @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann- 60lb gas pressure test on the roof ok
|
Pressure Test | 9/14/2018 | 9/14/2018 | 9/14/2018 | P | PASS |
Brian Scoles
|
|
|
if questions call Omar @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann- 20lb gas pass to fireplace
|
Pressure Test | 7/5/2018 | 7/6/2018 | 7/6/2018 | P | PASS |
Jack Reynolds
|
|
|
If questions contact Jerry Prough @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann- 20 lb gas pressure test ok
|
Pressure Test | 7/3/2018 | 7/5/2018 | 7/5/2018 | A | FAIL |
Brian Scoles
|
|
|
if questions call Jerry @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann- gauge at fireplace below 20psi- tried to call Jerry no answer
|
Issue PAID IN FULL permit | | | 7/3/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/3/2018 | | DONE |
|
|
|
This permit was created on the web by Stacia Haumann
|