DOC - Permit Finaled | 11/19/2018 | 11/19/2018 | 11/19/2018 | P | PASS |
Jack Reynolds
|
|
|
gas piping final ok
|
Pressure Test | 7/20/2018 | 7/20/2018 | 7/20/2018 | P | PASS |
Jack Reynolds
|
|
|
Re-inspect pressure test. Please call Devon at K;T Contracting at ###-#### while onsite for this inspection. Phone #: ###-#### Inspection requested via web by Jamee Shoecraft - 20lb gas pressure test ok
|
Pressure Test | 7/18/2018 | 7/19/2018 | 7/19/2018 | A | FAIL |
Jack Reynolds
|
|
|
Re-inspection - pressure test Phone #: ###-#### Inspection requested via web by Jamee Shoecraft- pressure gauage was at zero- also the flex gasline that runs in the crawl space has exposed flex next to fittings, needs protective tape ( this is next to the crawl access in the laundry room)
|
Pressure Test | 7/16/2018 | 7/17/2018 | 7/17/2018 | A | FAIL |
Jack Reynolds
|
|
|
Pressure test Phone #: ###-#### Inspection requested via web by Jamee Shoecraft- 20lb gas pressure test fail gauge was at zero
|
Pressure Test | 7/9/2018 | 7/10/2018 | 7/10/2018 | A | FAIL |
Jack Reynolds
|
|
|
Owner contact information - Gae Peyron - ###-#### Phone #: ###-#### Inspection requested via web by Jamee Shoecraft-- gasline outside is laying on the ground needs to be supported and 3.5" off the ground- Flex gas line in the fireplace needs black protective coating extended to fitting bare flex can't be showing. this is the case at the outdoor connection aswell- need double valve with open ended tee between the two valves at the tie in location near the meter
|
Issue PAID IN FULL permit | | | 7/9/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/9/2018 | | DONE |
|
|
|
This permit was created on the web by Jamee Shoecraft
|