Mec-Aging Inspection | 6/27/2019 | 6/27/2019 | 6/27/2019 | | PASS |
Jack Reynolds
|
|
|
-permit expired ok
|
DOC - Permit Expired | 6/27/2019 | 6/27/2019 | 6/27/2019 | A | PASS |
Jack Reynolds
|
|
|
- permit expired ok - permit not active since 7/13/2018
|
Mec-Aging Inspection | 3/28/2019 | 3/28/2019 | 3/28/2019 | | DONE |
Jack Reynolds
|
|
|
Called western and talked with office about their mechanical aging permit. schedule inspection with homeowner if work is finished. Permit will expire in 180 days if not active
|
Final | 7/11/2018 | 7/13/2018 | 7/13/2018 | A | FAIL |
Jack Reynolds
|
|
|
homeowner # ###-#### - michael thank you! Phone #: ###-#### Inspection requested via web by Aaron Alandt- need to place another combustion air vent in door( front of furnace)- lineset has a rip in the insulation above the water heater- above the water heater has building insulation touching the common vent(flue) need 1" clearances- lineset is also within 1" of the furnace flue near the water heater- A/C breaker size is too large needs to be a 25amp
|
Final | 7/10/2018 | 7/11/2018 | 7/11/2018 | P | NR |
Chad Schwendiman
|
|
|
INSTALLER SCOTT ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
|
Issue PAID IN FULL permit | | | 7/10/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/10/2018 | | DONE |
|
|
|
This permit was created on the web by Aaron Alandt
|