Final | 10/12/2018 | 10/12/2018 | 10/12/2018 | P | PASS |
Ben Livingston
|
|
|
OPEN JOB SITE, NO NEED TO CALL AND I HAD MY INSTALLER CALL YOU EARLIER TO MAKE SURE WE HAD EVERYTHING DONE. CALL ME AT OFFICE NUMBER PROVIDED IF ANY FURTHER CONCERNS OR QUESTIONS. MY NAME IS STEVE WITH DIAMOND HEATING Phone #: ###-#### Inspection requested via web by Rick Montgomery
|
Final | 10/4/2018 | 10/4/2018 | 10/4/2018 | P | FAIL |
Ben Livingston
|
|
|
CORRECTIONS HAVE BEEN MADE AND READY FOR RE-INSPECTION. OPEN JOB SITE AND YOU CAN GO ANYTIME. I LEFT MY OFFICE NUMBER IN CASE YOU HAVE ANY TROUBLES OR QUESTIONS, MY NAME IS STEVE DALE WITH DIAMOND HEATING Phone #: ###-#### Inspection requested via web by Rick Montgomery 3 of the splits dont have corrections made on the condensate lines
|
Final | 9/20/2018 | 9/21/2018 | 9/21/2018 | A | FAIL |
Ben Livingston
|
|
|
open jobsite but our job portion is 100% completed for our scope of work. You dont need to call anyone and you can access anytime, setting for AM request. If you have any questions, please call me at Diamond Office number listed above, my name is Steve Dale Phone #: ###-#### Inspection requested via web by Rick Montgomery 3/8" flex tubing not approved material, condensate needs to be run down to the ground to an approved location, condensate cannot be run to a walkway, armaflex needs UV protection, line sets need more supports
|
Issue PAID IN FULL permit | | | 7/18/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/18/2018 | | DONE |
|
|
|
This permit was created on the web by Rick Montgomery
|
First Notice | 10/12/2018 | 10/12/2018 | | | |
Ben Livingston
|
|
|
|