Final | 10/17/2018 | 10/18/2018 | 10/18/2018 | A | PASS |
Jack Reynolds
|
|
|
if house is locked, lock box on water spout on side of house. Code is 2010 Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek- final ok - Max your air balance certification has expired in 2017 and needs to be taken care of for future air balances
|
Rough-in | 7/31/2018 | 7/31/2018 | 7/31/2018 | A | PASS |
Jack Reynolds
|
|
|
Inspection requested via web by Floyd Floyd Peek- water heater flue ok- R/I ok - 20lb gas pressure test ok- 5lb flue pressure ok
|
Rough-in | 7/29/2018 | 7/30/2018 | 7/30/2018 | A | PART |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek- Need to see approved firestops put in place at ceiling and floor for water heater bw flue vent
|
Rough-in | 7/26/2018 | 7/27/2018 | 7/27/2018 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek -BW vent for water heater needs 1" clearances- orange spray foam needs to be removed along with any other sealer at floor and ceiling and manufacturers firestop needs to be put in place and ceiling and floor- metal ducting in crawl and attic need to be insulated - flex runs in attic have rips that need fixed -flex gas line in crawl needs more supports
|
Issue PAID IN FULL permit | | | 7/26/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/26/2018 | | DONE |
|
|
|
This permit was created on the web by Floyd Floyd Peek
|