Permit Information
Permit NumberMEC18-03753
StatusFinaled
Name ELITE SYSTEMS
Site Address 12684 W IRVING ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete HVAC Installation: Installing AC, Furnace and duct work. No Fireplaces
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/7/201811/8/201811/8/2018APASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Kim Evans- final ok
Rough-in8/6/20188/6/20188/6/2018PPASS
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Devony Bullard- R/I ok- 20lb gas pressure test ok
Rough-in8/2/20188/3/20188/3/2018PFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Devony Bullard- supply run above front door still needs flex fixed- lineset coming down exterior wall needs fixed- duct work at furnace needs sealed
Rough-in8/2/20188/3/20188/2/2018ACANC
DetailsBrian Scoles
Phone #: ###-#### >> Inspection requested via web by Devony Bullard Inspection cancelled from web by: Devony Bullard
Rough-in7/31/20188/1/20188/1/2018AFAIL
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Devony Bullard
- b vent clearances need 1" upstairs- cant see clearances on b vent downstairs through floor
-supply flex downstairs is being pinched by support
-need duct seal at furnace
-need to see framing finshed upstairs
-some flex runs upstairs have sharp bends at the 90 degree turns
Pressure Test7/31/20188/1/20188/1/2018APASS
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by Devony Bullard- 20lb gas pressure test ok
Issue PAID IN FULL permit  7/31/2018 DONE
Payment received via Govolutions
Application received  7/31/2018 DONE
This permit was created on the web by Devony Bullard