Final | 10/10/2018 | 10/10/2018 | 10/10/2018 | P | PASS |
Jack Reynolds
|
|
|
Call William with any problems ###-#### Phone #: ###-#### Inspection requested via web by Aaron Toomey- final ok
|
Final | 10/9/2018 | 10/10/2018 | 10/10/2018 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey- need air balance report onsite
|
Rough-in | 8/7/2018 | 8/7/2018 | 8/7/2018 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey- R/I ok
|
Rough-in | 8/6/2018 | 8/7/2018 | 8/7/2018 | A | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey- inside return duct needs sealed and fresh air duct at return needs sealed (duct has large gaps)
|
Rough-in | 8/3/2018 | 8/3/2018 | 8/3/2018 | P | NR |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey- crawl not finished- lineset not roughed in- indoor equipment not set-
|
Pressure Test | 8/3/2018 | 8/3/2018 | 8/3/2018 | P | PASS |
Jack Reynolds
|
|
|
and fireplace Phone #: ###-#### Inspection requested via web by Aaron Toomey- 20lb gas pressure test ok- 5lb flue pressure test ok
|
Issue PAID IN FULL permit | | | 8/3/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/1/2018 | | DONE |
|
|
|
This permit was created on the web by Aaron Toomey
|