Final | 4/1/2019 | 4/2/2019 | 4/2/2019 | P | PASS |
Brian Scoles
|
|
|
GARAGE CODE 8100 Phone #: ###-#### Inspection requested via web by Oleg Chervak- fireplace and HVAC final ok
|
Final | 3/15/2019 | 3/18/2019 | 3/18/2019 | P | FAIL |
Brian Scoles
|
|
|
side door will be open, Phone #: ###-#### Inspection requested via web by Oleg Chervak- need uv protection on lineset outside- need range hood installed and vented- need fireplace finished and mantel installed- need 1" clearance on b vent for water heater flue at ceiling and water heater installed and vented
|
Rough-in | 8/24/2018 | 8/24/2018 | 8/24/2018 | P | PASS |
Brian Scoles
|
|
|
MEC AND FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak- fireplace R/I ok- HVAC R/I ok
|
Rough-in | 8/23/2018 | 8/23/2018 | 8/23/2018 | P | FAIL |
Brian Scoles
|
|
|
mec and firepl Phone #: ###-#### Inspection requested via web by Oleg Chervak- need approved manual j onsite couldnt find one- flue doesnt have 1" clearance to combustibles at roof and flue needs supported- insulation shield laying against pipe- fireplace still not completed or firecaulked- 1st floor bath exhaust needs flex ran out none there- left correction notice back window
|
Rough-in | 8/19/2018 | 8/20/2018 | 8/20/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- need acca report onsite couldnt find one- 2nd floor exhaust fan just hanging out between trusses- are you doing fireplace? if so needs completed- water heater b vent laying in garage against supply duct not installed
|
Pressure Test | 8/19/2018 | 8/20/2018 | 8/20/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass
|
Issue PAID IN FULL permit | | | 8/14/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/14/2018 | | DONE |
|
|
|
This permit was created on the web by Oleg Chervak
|