Final | 9/5/2018 | 9/6/2018 | 9/6/2018 | P | PASS |
Ben Livingston
|
|
|
Please call owner Paula on the way, ###-#### Phone #: ###-#### Inspection requested via web by Shauna Llewellyn
|
Final | 8/28/2018 | 8/29/2018 | 8/29/2018 | P | FAIL |
Ben Livingston
|
|
|
Please call homeowner Paula on the way, ###-####. The 3/8" vinyl tubing isn''t used as the drain, the 3/4" PVC above the garage window is per homeowner request. Phone #: ###-#### Inspection requested via web by Shauna Llewellyn IRC 2012 M1411.3 condensate shall not dischargeinto a street or alley,or where it would cuase a nuisence.
|
Final | 8/24/2018 | 8/27/2018 | 8/27/2018 | P | FAIL |
Ben Livingston
|
|
|
Please call homeowner Paula on the way, ###-#### Phone #: ###-#### Inspection requested via web by Shauna Llewellyn plastic flex tubing not approved condensate material
|
Issue PAID IN FULL permit | | | 8/20/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/20/2018 | | DONE |
|
|
|
This permit was created on the web by Shauna Llewellyn
|