Rough-in | 10/22/2018 | 10/23/2018 | 10/23/2018 | P | DONE |
Jack Reynolds
|
|
|
Anne Phone #: ###-####- this inspection I think should have been a final- i reschedule as a final
|
Final | 10/23/2018 | 10/23/2018 | 10/23/2018 | P | PASS |
Jack Reynolds
|
|
|
Anne Phone #: ###-####- fireplace final ok
|
Rough-in | 9/12/2018 | 9/12/2018 | 9/12/2018 | P | PASS |
Jack Reynolds
|
|
|
Cas Lawler point of contact. Please call 30 min prior to inspection Phone #: ###-#### Inspection requested via web by Sheldon Lebow- vent piping clearances ok- framing around vent pipe ok- R/I ok
|
Rough-in | 8/28/2018 | 8/29/2018 | 8/29/2018 | A | FAIL |
Jack Reynolds
|
|
|
Kaz Lawler is point of contact Phone #: ###-#### Inspection requested via web by Sheldon Lebow- horizantal flue pipe running in the floor above needs 3 " clearances to combustibles- need to see framing finished by homeowner at fireplace
|
Issue PAID IN FULL permit | | | 8/28/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/28/2018 | | DONE |
|
|
|
This permit was created on the web by Sheldon Lebow
|