First Notice | 4/18/2019 | 4/18/2019 | 6/24/2019 | | DONE |
Ben Livingston
|
|
|
|
Print Statement | | | 6/24/2019 | | DONE |
|
|
|
|
Final | 4/17/2019 | 4/18/2019 | 4/18/2019 | A | PASS |
Ben Livingston
|
|
|
Please Call Bryan at least one hour before inspection. Thank you so much! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Final | 4/9/2019 | 4/11/2019 | 4/11/2019 | A | FAIL |
Chad Schwendiman
|
|
|
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum 1) Need to label all fire damper access doors 2) Need to finish glueing and support condensate piping 3) Need UV protection on aramflex outdoors 4) Need to angle around fire damper openings in rated ceilings 5) Need to install missing exhaust fan grill 6) Need to extend dryer ducts outside of the wall 7) Need air balance report 8) Need to install A/C that was removed 9) Need letter from engineer for room usage change and removal of exhaust fan in oxygen storage
|
Rough-in | 3/26/2019 | 3/28/2019 | 3/28/2019 | P | PASS |
Ben Livingston
|
|
|
Please call Don, Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum above grid okay all rooms
|
Pressure Test | 3/20/2019 | 3/20/2019 | 3/20/2019 | P | CANC |
Eric Strole
|
|
|
Please call Mike, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Rough-in | 2/21/2019 | 2/22/2019 | 2/22/2019 | A | PASS |
Eric Strole
|
|
|
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum-area B pass.
|
Rough-in | 2/20/2019 | 2/21/2019 | 2/21/2019 | P | PART |
Eric Strole
|
|
|
Please call Bryan, thank YOU! Phone #: ###-#### Inspection requested via web by Rhonda Marcum-Area B duct seal ok. Need to fire caulk all ducts going thru all fire rated walls.
|
Rough-in | 2/13/2019 | 2/13/2019 | 2/13/2019 | P | PASS |
Jack Reynolds
|
|
|
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - area B caffateria and theater and corridor soffits with duct work ok for cover duct seal ok
|
Rough-in | 2/11/2019 | 2/11/2019 | 2/11/2019 | P | FAIL |
Jack Reynolds
|
|
|
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - not ready area B sofits- return sleeve needs finished one supply linear can needs finished in theater room and duct sealed - found a few location that needed duct seal finished - two fuseable link dampers are possibly being moved out of fire rating. damper needs to stay in rated assembly. smaller duct will most likely need access doors to access fuseable link
|
Rough-in | 1/11/2019 | 1/14/2019 | 1/14/2019 | A | PASS |
Jack Reynolds
|
|
|
Please call Bryan, Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - 6 fire dampers in area B framing clearances and dry wall ok - 2 linesets R/I ok
|
Rough-in | 12/17/2018 | 12/18/2018 | 12/18/2018 | A | PASS |
Chad Schwendiman
|
|
|
Please call Bryan, Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Okay to sheetrock area c okay to insulate duct in joist space in area b
|
Rough-in | 12/11/2018 | 12/11/2018 | 12/11/2018 | P | PASS |
Chad Schwendiman
|
|
|
Please call Bryan, Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Okay to sheetrock area D
|
Rough-in | 12/7/2018 | 12/10/2018 | 12/10/2018 | A | FAIL |
Chad Schwendiman
|
|
|
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Need to install retaining angles on fire dampers per instructions
|
Pressure Test | 12/5/2018 | 12/5/2018 | 12/5/2018 | P | PASS |
Jack Reynolds
|
|
|
Please call Dave, Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - 60lb gas pressure test on building b,c,d ok - talked with dave about making sure to support gas piping per specs through out building
|
Pressure Test | 12/4/2018 | 12/4/2018 | 12/4/2018 | P | FAIL |
Chad Schwendiman
|
|
|
Please call Dave, Thank YOU! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - not holding pressure
|
Rough-in | 11/30/2018 | 12/3/2018 | 12/3/2018 | A | PART |
Chad Schwendiman
|
|
|
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Okay to insulate duct in area D, exhaust fans in area D okay. Okay to sheet rock ceiling in west area
|
Rough-in | 11/29/2018 | 11/30/2018 | 11/30/2018 | A | FAIL |
Chad Schwendiman
|
|
|
Please call Bryan ###-####. thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Need fire/smoke damper installaion instructions to verify expansion clearances
|
Pressure Test | 11/27/2018 | 11/27/2018 | 11/27/2018 | P | PASS |
Chad Schwendiman
|
|
|
Call Dave, Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - 60lb gas pass for temp heat
|
Rough-in | 11/7/2018 | 11/8/2018 | 11/8/2018 | A | PART |
Chad Schwendiman
|
|
|
We need a R/I for Area A, please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Okay to cover ceilings in area A except for around fire dampers in the hallway
|
Rough-in | 10/29/2018 | 10/29/2018 | 10/29/2018 | P | CANC |
Ben Livingston
|
|
|
Please call Dave, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum called under wrong permit
|
Rough-in | 10/25/2018 | 10/26/2018 | 10/26/2018 | A | PART |
Eric Strole
|
|
|
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum-Area A, C & D corridor overhead duct seal pass. OK to insulate.
|
Pressure Test | 10/19/2018 | 10/19/2018 | 10/19/2018 | P | PART |
Eric Strole
|
|
|
Please call Dave, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum-20 lb gas test on 3/4 line from area B to furnace in area A pass.
|
Pressure Test | 10/18/2018 | 10/18/2018 | 10/18/2018 | P | FAIL |
Eric Strole
|
|
|
Please call Dave, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum-gas test fail.
|
Conference | 10/15/2018 | 10/16/2018 | 10/16/2018 | P | PASS |
Ben Livingston
|
|
|
1pm
|
Pressure Test | 10/16/2018 | 10/16/2018 | 10/16/2018 | P | NR |
Eric Strole
|
|
|
Please call Dave, Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum-Not ready.
|
Conference | 10/15/2018 | 10/16/2018 | 10/16/2018 | P | DONE |
Eric Strole
|
|
|
Please call Bryan ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum-Conferance on fire/smoke dampers.
|
Pressure Test | 10/15/2018 | 10/16/2018 | 10/16/2018 | A | FAIL |
Eric Strole
|
|
|
Please call Dave, Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum-Gauge will not zero out & 1/2" csst at 160' is undersized.
|
Conference | 10/15/2018 | 10/15/2018 | 10/15/2018 | P | CANC |
Ben Livingston
|
|
|
Please call Bryan ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Issue PAID IN FULL permit | | | 9/28/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/28/2018 | | DONE |
|
|
|
This permit was created on the web by Rhonda Marcum
|