Final | 2/21/2019 | 2/22/2019 | 2/22/2019 | A | PASS |
Ben Livingston
|
|
|
mac fireplace final 7285 Phone #: ###-#### Inspection requested via web by Oleg Chervak
|
Final | 2/18/2019 | 2/19/2019 | 2/19/2019 | P | NH |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak no access
|
Final | 2/13/2019 | 2/13/2019 | 2/13/2019 | P | FAIL |
Brian Scoles
|
|
|
MEC AND FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak- need approved manual j onsite couldnt find one- need to remove stucco around gas piping at meter location and seal weather tight- fireplace shut off valve needs to be readily accessible- fresh air duct to return air plenum needs insulated
|
Pressure Test | 10/12/2018 | 10/12/2018 | 10/12/2018 | A | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak
|
Rough-in | 10/12/2018 | 10/12/2018 | 10/12/2018 | A | PASS |
Ben Livingston
|
|
|
FIREPL AND MEC Phone #: ###-#### Inspection requested via web by Oleg Chervak rough in and fireplace
|
Pressure Test | 10/10/2018 | 10/11/2018 | 10/11/2018 | P | PEND |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak
|
Rough-in | 10/10/2018 | 10/11/2018 | 10/11/2018 | P | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak duct wrap needs to comply with code IRC M1601.3
|
Pressure Test | 10/11/2018 | 10/11/2018 | 10/11/2018 | P | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak 20lb, 5lb flue
|
Issue PAID IN FULL permit | | | 10/1/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/1/2018 | | DONE |
|
|
|
This permit was created on the web by Oleg Chervak
|