Final | 5/16/2019 | 5/17/2019 | 5/16/2019 | A | PASS |
Chad Schwendiman
|
|
|
Final for Pioneer Crossing - Call Lou ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery
|
Final | 5/14/2019 | 5/15/2019 | 5/15/2019 | A | FAIL |
Chad Schwendiman
|
|
|
Final for Pioneer Crossing - Please call Lou ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - Need uv protection on exposed arma flex, Need to remove sheetrock in front of duct heater access
|
Rough-in | 5/9/2019 | 5/10/2019 | 5/10/2019 | A | PASS |
Chad Schwendiman
|
|
|
Cover for 3rd Floor - Call Lou ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover 3rd floor
|
Rough-in | 5/8/2019 | 5/9/2019 | 5/9/2019 | A | FAIL |
Chad Schwendiman
|
|
|
Cover for 4th floor - call Lou ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - Fan coil unit needs to be moved from above wall. Duct heater needs to be moved so wall does not interfer with access panel
|
Rough-in | 4/30/2019 | 5/1/2019 | 5/1/2019 | A | PASS |
Chad Schwendiman
|
|
|
Cover inspection for 1st floor. Please call Lou at ###-#### prior to arrival. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Okay to cover 1st floor grid ceiling
|
Rough-in | 4/25/2019 | 4/26/2019 | 4/26/2019 | P | PASS |
Chad Schwendiman
|
|
|
Cover for 2nd floor call Lou ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - 2nd floor okay to cover grid ceiling
|
Rough-in | 3/8/2019 | 3/8/2019 | 3/8/2019 | P | PASS |
Ben Livingston
|
|
|
Re-inspection - cover for 5th floor bathrooms. Call Daryl ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery 5th floor restroom okay
|
Rough-in | 3/7/2019 | 3/8/2019 | 3/8/2019 | A | FAIL |
Ben Livingston
|
|
|
Cover for 5th floor bathroom. Call Daryl Hulse ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery 5th floor fire smoke damper angle not to manufactures instalation instructions
|
Rough-in | 3/5/2019 | 3/6/2019 | 3/6/2019 | A | PASS |
Chad Schwendiman
|
|
|
Smoke/Fire damper inspection - call Daryl ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - Expansion clearance okay on fire/smoke dampers coming out of the shaft on the 2nd-5th floors.
|
Rough-in | 2/21/2019 | 2/22/2019 | 2/22/2019 | A | PASS |
Chad Schwendiman
|
|
|
5th floor bathroom for insulation, call Daryl ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - Okay to insulate ductwork in 5th floor bathroom
|
Rough-in | 2/7/2019 | 2/7/2019 | 2/7/2019 | P | PASS |
Jack Reynolds
|
|
|
Trim smoke fire dampers 3rd ; 4th floor bathrooms - call Daryl ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - 3rd and 4th floor smoke fire damper trim ok - bathrooms on 3rd and 4th floor ceiling cover ok
|
Rough-in | 2/6/2019 | 2/7/2019 | 2/7/2019 | A | PART |
Jack Reynolds
|
|
|
Cover for 3rd and 4th floor bathrooms Phone #: ###-#### Inspection requested via web by Heather Gransbery - need to see trim around fire dampers on 3rd and 4th floor before cover of bathrooms
|
Rough-in | 2/4/2019 | 2/5/2019 | 2/5/2019 | A | PASS |
Ben Livingston
|
|
|
4th floor bathroom for insulation - please call Daryl ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery 4th floor bathroom duct seal
|
Conference | 2/5/2019 | 2/5/2019 | 2/5/2019 | P | FAIL |
Ben Livingston
|
|
|
4th floor bathroom for insulation - please call Daryl ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery 4th 3rd and 2nd floor fire smoke dampers need tobe installed per manufactures instruction
|
Rough-in | 1/30/2019 | 1/31/2019 | 1/31/2019 | A | PART |
Ben Livingston
|
|
|
cover for 2nd floor bathroom. Phone #: ###-#### Inspection requested via web by Heather Gransbery 2nd floor bathroom okay, 2nd floor fire damper framing clearence okay
|
Rough-in | 1/25/2019 | 1/28/2019 | 1/28/2019 | A | FAIL |
Ben Livingston
|
|
|
2nd floor bathrooms cover, 3rd floor bathrooms insulation. Please call Daryl ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery 2nd and 3rdfloor duct seal okay, 2nd floor insulation and lids not rdy for cover, firesmoke dampers 2nd and 3rd floor need to be framed in per installation instructions
|
Rough-in | 1/18/2019 | 1/22/2019 | 1/22/2019 | A | PASS |
Chad Schwendiman
|
|
|
2nd floor bathroom and 1st floor cover chase, call Daryl ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - Okay to cover 1st floor shaft, okay to insulate duct work in 2nd floor bathrooms
|
Rough-in | 1/14/2019 | 1/15/2019 | 1/15/2019 | A | PASS |
Chad Schwendiman
|
|
|
Cover for 1st floor bathroom. Please call Daryl with questions ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Okay to cover 1st floor bathrooms
|
Rough-in | 12/27/2018 | 12/28/2018 | 12/28/2018 | A | PASS |
Troy James
|
|
|
Bathroom Inspection, please call Derek Rome ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery Okay to insulate the ducts at first floor restrooms.
|
Rough-in | 12/12/2018 | 12/12/2018 | 12/12/2018 | A | PART |
Chad Schwendiman
|
|
|
Insulation inspection for Pioneer Crossing - Call Derek Rome ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - Okay to insulate make-up air loop on 1st floor and shaft duct work
|
Issue PAID IN FULL permit | | | 10/17/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/17/2018 | | DONE |
|
|
|
This permit was created on the web by Heather Gransbery
|
First Notice | 5/16/2019 | 5/16/2019 | | | |
Chad Schwendiman
|
|
|
|