Final | 4/12/2019 | 4/12/2019 | 4/12/2019 | P | PASS |
Jack Reynolds
|
|
|
Call Jason @ ###-#### with any issues. Phone #: ###-#### Inspection requested via web by Angie Maguire - final ok
|
Final | 4/5/2019 | 4/5/2019 | 4/5/2019 | P | FAIL |
Jack Reynolds
|
|
|
Lock box code for entry is 1108. Call Jason @ ###-#### with any issues. Phone #: ###-#### Inspection requested via web by Angie Maguire - need air balance report/ duct blast report/ and stamped man J onsite for final
|
Final | 4/5/2019 | 4/9/2019 | 4/5/2019 | A | CANC |
Jack Reynolds
|
|
|
Call Jason @ ###-#### with any issues. Phone #: ###-#### >> Inspection requested via web by Angie Maguire Inspection cancelled from web by: Angie Maguire
|
Rough-in | 11/2/2018 | 11/2/2018 | 11/2/2018 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- line set support ok- exhaust fans sealed- man j ok- R/I ok
|
Rough-in | 10/31/2018 | 11/1/2018 | 11/1/2018 | P | FAIL |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- need city approved man J- need to seal exhaust fan connection- support line set in wall and attic
|
Pressure Test | 10/31/2018 | 11/1/2018 | 11/1/2018 | P | PASS |
Jack Reynolds
|
|
|
Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- 5lb flue ok- 20lb gas ok
|
Issue PAID IN FULL permit | | | 10/31/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/31/2018 | | DONE |
|
|
|
This permit was created on the web by Dawn Kalsbeek
|