Final | 1/23/2019 | 1/24/2019 | 1/24/2019 | P | PASS |
Jack Reynolds
|
|
|
garage code: 7352 Phone #: ###-#### Inspection requested via web by Dan Otero - fireplace final ok
|
Rough-in | 11/7/2018 | 11/8/2018 | 11/8/2018 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Dan Otero
|
Issue PAID IN FULL permit | | | 11/6/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/6/2018 | | DONE |
|
|
|
This permit was created on the web by Dan Otero
|