Permit Information
Permit NumberMEC18-05451
StatusFinaled
Name COX MECHANICAL INC
Site Address 7070 W OVERLAND RD
Project Name 
Customer Number 
ePlanReviewNo
Description
New: furnish and indtall 2ea Trane RTUs with related duct .Furnish and install grease duct and RR duct
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/2/20191/3/20191/3/2019PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Robin Cox- final ok- card signed
Final12/28/201812/31/201812/31/2018APART
DetailsBrian Scoles
air balance report should be on site. if you need, i will email to you Phone #: ###-#### Inspection requested via web by Robin Cox- all equipment needs set and tethered- need to seal MAU ducting on roof weather tight missing seems and corners- air balance ok- temp occupancy ok- will final this permit out after other mech inspections are completed and correction is made- rest is good
Rough-in12/13/201812/14/201812/14/2018APASS
DetailsBrian Scoles
cover Phone #: ###-#### Inspection requested via web by Robin Cox- R/I ok- ceiling space registers flex and ducting ok to cover
Rough-in12/6/201812/6/201812/6/2018PPASS
DetailsBrian Scoles
mau duct seal ok- ok to insulate- 2nd layer firewrap ok- ok for ceiling grid
Rough-in12/2/201812/3/201812/3/2018APASS
DetailsBrian Scoles
light test for grease duct. please contact Robin to coordinate time as we are not on site. thanks, Robin 208*890*4261 Phone #: ###-#### Inspection requested via web by Robin Cox- light test pass- ok for first layer
Rough-in11/19/201811/20/201811/20/2018APASS
DetailsBrian Scoles
Duct seal inspection Phone #: ###-#### Inspection requested via web by Robin Cox- seal on supply r/a and exhaust duct ok- ok for insulation- insulation above hard lids ok- ok to sheetrock hard lids only- still needs hood and MAU duct inspected when installed
Rough-in11/15/201811/16/201811/16/2018APART
DetailsBrian Scoles
duct seal above sheetrock lids Phone #: ###-#### Inspection requested via web by Robin Cox- seal on exhaust and supply duct ok above bath rooms- ok to insulate- will look at insulation on next R/I inspection
Issue PAID IN FULL permit  11/11/2018 DONE
Payment received via Govolutions
Owner Supplied Equipment  11/11/2018  
Application received  11/11/2018 DONE
This permit was created on the web by Robin Cox
First Notice1/3/20191/3/2019   
DetailsBrian Scoles