First Notice | 7/18/2019 | 7/18/2019 | 8/12/2019 | | DONE |
Brian Scoles
|
|
|
|
Final | 7/18/2019 | 7/18/2019 | 7/18/2019 | P | PASS |
Brian Scoles
|
|
|
final ok- card signed
|
Rough-in | 7/17/2019 | 7/18/2019 | 7/18/2019 | P | PASS |
Brian Scoles
|
|
|
Inspection requested for Thursday PM. Please contact Scott before coming out ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery- R/I ok on b vent thru roof-
|
Rough-in | 7/16/2019 | 7/19/2019 | 7/17/2019 | A | CANC |
Brian Scoles
|
|
|
Inspection requested for Friday AM. Please contact Scott before coming out ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
|
Rough-in | 6/5/2019 | 6/7/2019 | 6/7/2019 | A | PART |
Brian Scoles
|
|
|
Final inspection for TCO. Please call Scott at ###-#### prior to arrival on-site. Phone #: ###-#### Inspection requested via web by Heather Gransbery- need copy of engineer approval with signature and stamp on elevator room and and unit heaters installs to final out- Rest is good- temp occupancy ok
|
Final | 5/29/2019 | 5/31/2019 | 5/31/2019 | P | PART |
Brian Scoles
|
|
|
Final Inspection. Please contact Scott at ###-#### prior to arrival on-site. Phone #: ###-#### Inspection requested via web by Heather Gransbery- need engineer approval on fire dampers installed in elevator equipment room for whats installed- need installation instruction on roofing boots used with bvent on roof- unit heater on mezz needs 1/4" per foot rise to outside- temp occupancy ok
|
Rough-in | 5/21/2019 | 5/22/2019 | 5/22/2019 | A | PART |
Brian Scoles
|
|
|
Inspection for CJD to cover the offices. Please call Scott before coming out ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery- 1st floor offices ok for ceiling tiles- fire damper installed in concrete floor will not be in rated assembly when fire rated ceiling is installed need engineer to address issue since center block wall not going up to ceiling
|
Rough-in | 5/20/2019 | 5/21/2019 | 5/21/2019 | A | FAIL |
Brian Scoles
|
|
|
Inspection for a tile cover in the office area. Please contact Scott at ###-#### prior to arrival on-site. Phone #: ###-#### Inspection requested via web by Heather Gransbery- 4 offices north side 1st floor need supply flex lengthened pinched off at tap
|
Rough-in | 5/16/2019 | 5/17/2019 | 5/17/2019 | A | PASS |
Brian Scoles
|
|
|
Inspection for temp cover above mezz deck. Please contact Scott at ###-#### prior to arrival on-site Phone #: ###-#### Inspection requested via web by Heather Gransbery- RTU 1 and 2 seal on duct 2nd floor mezz ok- ok to cover shaft
|
Rough-in | 5/8/2019 | 5/10/2019 | 5/10/2019 | A | PART |
Brian Scoles
|
|
|
Inspection for CJD above mezzanine to get a temp cover on shaft walls. Please call Scott before coming out - ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery- 3 shafts 2nd floor seal on duct ok to cover
|
Rough-in | 4/30/2019 | 5/1/2019 | 5/1/2019 | A | PART |
Brian Scoles
|
|
|
Cover inspection for offices. Please call Scott at ###-#### prior to arrival. Phone #: ###-#### Inspection requested via web by Heather Gransbery- office and bathroom area seal on all duct ok- ok to cover
|
Issue PAID IN FULL permit | | | 11/12/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/12/2018 | | DONE |
|
|
|
This permit was created on the web by Heather Gransbery
|